Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T20CM02646
Parcel: 116141350

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T20CM02646
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2025 Residential Building - Standard APPROVED
06/13/2025 Site Engineering - Standard NOT REQUIRED
06/16/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/16/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Steve Shields
Section Manager

PROJECT: T20CM02646
2040 W Calle Placida
Detached Porch in Front Yard.
Residential (3rd Review)

TRANSMITTAL DATE: June 16, 2025

Provide a detailed response letter with your next submittal that clearly shows how you have addressed all Zoning comments.

This site is located in the R-1 zone (UDC 4.7.1). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9. 10.

1. This comment was not addressed correctly. Per Construction Plan I-826 sheet 3, found at” https://maps-and-records.tucsonaz.gov/construction-plans/details/I-826, the distance from face of curb to the property line is 7’. Provide a dimension from the center line of Calle Placida to the curb and a dimension from the curb to the street property line.

2. This comment was not addressed. Provide a lot coverage calculation that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example. Provide a lot coverage calculation on the plan.

3. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of less than 9’-0” the required perimeter yard setback to the west property line is 6’-0” proposed is 3’-0”. At a minimum a neighbors setback waiver is required to reduce the setback to 3’-0”, UDC Article 6.6.2.D. To secure this neighbor’s setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at_______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan.

Signature: _____________________________

Date: _________________________________
If you are not able to secure this waiver a Design Development Option (DDO) to reduce the setback will need to be submitted and approved. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov”.

Residential plot plan requirements can be found at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/15/2025 PDSD Application Completeness Express REVIEW COMPLETED