Permit Number: T18CM09741
Parcel: 13317064A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL REVISION v.1

Permit Number - T18CM09741
Review Name: COMMERCIAL REVIEW - FULL REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/28/2025 Site Zoning Standard APPROVED
03/28/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/21/2025 Commercial Building Standard REQUIRES RESUBMIT March 21, 2025
1st Review

Bright Design Associates
Attn: Rick Bright
660 S. Country Club
Tucson, Arizona 85716

Re: HERITAGE OAKS ASSITED LIVING
TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: T18CM09741
Stantec Project Number: 185215066
Stantec File Number: TUC-25-036

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-4 V-B 7,926 43 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Prefabricated wood trusses.
Special Inspections: Epoxy anchors.

ARCHITECTURAL COMMENTS

General

1. The plans are labeled “PRELIMINARY NOT FOR CONSTRUCTION”. Please provide 100% complete plans for construction.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please label the roof top units to correlate with the equipment schedule on sheet M0.1.

2. Please provide an updated energy conservation compliance report for the new mechanical units. [Ref. IECC 2018 Sec.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/21/2025 Commercial Electrical Standard REQUIRES RESUBMIT March 21, 2025
1st Review

Bright Design Associates
Attn: Rick Bright
660 S. Country Club
Tucson, Arizona 85716

Re: HERITAGE OAKS ASSITED LIVING
TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: T18CM09741
Stantec Project Number: 185215066
Stantec File Number: TUC-25-036

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-4 V-B 7,926 43 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Prefabricated wood trusses.
Special Inspections: Epoxy anchors.

ARCHITECTURAL COMMENTS

General

1. The plans are labeled “PRELIMINARY NOT FOR CONSTRUCTION”. Please provide 100% complete plans for construction.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please label the roof top units to correlate with the equipment schedule on sheet M0.1.

2. Please provide an updated energy conservation compliance report for the new mechanical units. [Ref. IECC 2018 Sec.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/21/2025 Commercial Mechanical Standard REQUIRES RESUBMIT March 21, 2025
1st Review

Bright Design Associates
Attn: Rick Bright
660 S. Country Club
Tucson, Arizona 85716

Re: HERITAGE OAKS ASSITED LIVING
TENANT IMPROVEMENT (REVISIONS)

City of Tucson Permit Number: T18CM09741
Stantec Project Number: 185215066
Stantec File Number: TUC-25-036

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
R-4 V-B 7,926 43 Yes Yes
Separate Permits: Automatic fire sprinklers and fire alarm.
Deferred Submittals: Prefabricated wood trusses.
Special Inspections: Epoxy anchors.

ARCHITECTURAL COMMENTS

General

1. The plans are labeled “PRELIMINARY NOT FOR CONSTRUCTION”. Please provide 100% complete plans for construction.

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

General

1. Please label the roof top units to correlate with the equipment schedule on sheet M0.1.

2. Please provide an updated energy conservation compliance report for the new mechanical units. [Ref. IECC 2018 Sec.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
03/18/2025 PDSD Application Completeness Express REVIEW COMPLETED