Permit Number: DP22-0147
Parcel: 14036006A

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.2

Permit Number - DP22-0147
Review Name: DEVELOPMENT PACKAGE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2023 CDRC Post Review PENDING ASSIGNMENT
01/19/2023 Fire New Construction REQUIRES RESUBMIT Building is 24,500 sq feet and regardless of the IBC fire sprinkler "out" the IFC has fire sprinkler requirement from the 2018 IFC, Chapter 9, Section 903.2.10. Along with the square footage 4,000 GPM. You shall install fire sprinklers and the one new hydrant being added shall supply 1,500 GPM for 2 hours.

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner