Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE NEW v.3
Permit Number - DP22-0105
Review Name: DEVELOPMENT PACKAGE NEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2025 | ROW Engineering Review Standard | APPROVED | |||
| 04/21/2025 | CDRC Post Review Express | PENDING ASSIGNMENT | |||
| 04/21/2025 | Commercial Plumbing Standard | REQUIRES RESUBMIT | This revision shows that the building 12 FFE (2994.50) is less than 12” above the rim level of MH #5 (2994.47) and will require a backwater valve. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson. | ||
| 04/21/2025 | TW New Development Review | REVIEW COMPLETED | DP22-0105 - Development Package NEW v3 - 8371 S HOUGHTON RD Tucson Water conditionally approves this submittal of the development package subject to the following condition. The public water main plans submitted to Tucson Water for this project under TDCO No. TW-WCP-0325-00018 will need to show: • The minimum and horizontal separations between the public water mains and the private water mains, as well as show the minimum vertical and horizontal separations between the public water mains and the public sewers. Note: Tucson Water requires the minimum vertical and horizontal separations between public water mains and private water mains to be the same as that required between public water mains and public sewers. In other words, the required the minimum vertical and horizontal separations between public water mains and private water mains is per Tucson Water Standard Detail SD-105. • Two (2) 6” GATE VALVES, B & C in each 6” fire service. One at the connection to the public water main, and one at the point where the fire service exits the public water easement. Any questions, comments or concerns about these comments may be directed to: Tim Rowe, P.E., Civil Engineer Tucson Water, New Development Section 201 N. Stone Avenue, #2-220 P.O. Box 27210 Tucson, AZ 85726-7210 (520) 837-2106 tim.rowe@tucsonaz.gov |