Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE REVIEW v.1
Permit Number - DP22-0099
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/23/2023 | Commercial Plumbing | APPROVED | |||
12/23/2022 | NPPO | APPROVED | |||
01/06/2023 | Site Engineering | APPROVED | |||
12/23/2022 | Site Landscape | APPROVED | |||
01/03/2023 | Site Zoning | APPROVED | |||
02/06/2023 | CDRC Post Review | PENDING ASSIGNMENT | |||
01/10/2023 | Fire New Construction | REQUIRES RESUBMIT | 3 hydrants within 400' of all the building are required due to new size being 8,040 sq ft. The hydrants do not meet the 400' requirements. You shall install fire sprinklers in the buildings. Also, Tucson Water only lets us pull 1,000 GPM from a hydrant, so you have 3,000 GPM between all the hydrants. Although that may be enough GPM for the buildings you have exceeded the distance requirements. Questions: Jennifer Peel-Davis Tucson Fire Department Fire Plans Examiner Fire Inspector I, II and Fire Alarm Plans Examiner Jennifer.Peel-Davis@Tucsonaz.gov Desk: 520-837-7033 |
||
02/06/2023 | External Reviewers - PC RFCD | REVIEW COMPLETED | From: Jeffrey Graupmann <Jeffrey.Graupmann@pima.gov> Sent: Monday, February 6, 2023 1:03 PM To: CDRC <CDRC@tucsonaz.gov>; James Janecek <James.Janecek@pima.gov> Subject: [EXTERNAL] RE: Request for RFCD review: DP22-0099 Looking at the submitted plans, it looks like everything is staying out of the RFCD Drainageway. We do not have any comments for this plan set. Jeff |
||
01/24/2023 | ROW Engineering Review | REVIEW COMPLETED | No Comments | ||
01/04/2023 | Traffic Engineering Review | REVIEW COMPLETED | 1. A PIA is going to be required for this project. https://www.tucsonaz.gov/tdot/private-improvement-agreement Contact TDOT Engineering for information. DOT-Engineering-Review-Section@tucsonaz.gov Or call. 520-791-5100 Jesus Villezcas |