Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: DP22-0027
Parcel: 132131380

Address:
1500 E 36TH ST

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.1

Permit Number - DP22-0027
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/30/2022 External Reviewers - Pima County Addressing APPROVED Good afternoon,



Pima County Addressing approves DP22-0027 Tent. Plat SFR at the Bridges B-1.





Thank you



Nicholas Jordan

Site Review Project Manager - Addressing Official

Pima County Development Services Department

201 N Stone AV – 1st Floor

Tucson, AZ 85701

(520) 724-9623
11/30/2022 External Reviewers - Tucson Airport Authority APPROVED November 30, 2022
City of Tucson
Planning and Development Services
201 North Stone Avenue, Third Floor
Tucson, AZ. 85701
RE: DP22-0027 / Tentative Plat - SFR at The Bridges B-1. Lots 1 thru 126,
and Common Areas "A" (private streets, utilities), and "B" thru "L" (open space, drainage,
utilities), 2
nd submittal, Received November 30, 2022
Dear Ms. Beasley,
Thank you for the opportunity to comment on DP22-0027, Tentative Plat – SFR at the Bridges
B-1; 2
nd Submittal, a development package application for an approximately 12.02 acre site,
located southwest of the intersection of East 36th Street and South Martin Luther King Jr Way.
The property is zoned Planned Area Development 15 (PAD-15), with the proposed use being a
single family residential development.
This site is within the Tucson International Airport avigation easement requirements and public
disclosure area, FAA traffic pattern airspace, and FAA Part 77 airspace.
The Tucson Airport Authority approves the 2nd submittal of this project and has no additional
comments to provide.
Please do not hesitate to contact me if you have any questions or concerns regarding this
comment letter. I can be reached by email at srobidoux@flytucson.com or by telephone at 520-
573-4811.
Respectfully,
Scott Robidoux, C.M.
Manager of Planning
11/16/2022 Site Landscape APPROVED
11/16/2022 NPPO NOT REQUIRED
11/30/2022 CDRC Post Review PENDING ASSIGNMENT
11/15/2022 Commercial Plumbing REQUIRES RESUBMIT While the FFE for 21 lots was revised on the resubmitted drawings, lots 40, 41, and 42 remained unchanged and still require backwater valves. Meanwhile, lot 107 no longer needs a backwater valve since the FFE was increased from 2467.75 to 2467.85, which is greater than 12” above the rim elevation of the next upstream manhole. [Initial comment: For lots 40, 41, and 42, the rim elevation of the next upstream sanitary manhole (2466.90’) is less than 12” below the first floor elevations. Provide for the installation of a backwater valve at these lots when future plumbing activities take place. Reference: Section 714.1, IPC 2018, as amended by the City of Tucson.]
11/21/2022 Site Engineering REQUIRES RESUBMIT Please provide explanation of typical lot grading details as added on Sheet 10. FFE & FG =1.00 is not clear.
See Zoning Comments.
Joshua Garcia
joshua.garcia@tucsonaz.gov
11/10/2022 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL



FROM: PDSD Zoning Review



PROJECT: Tentative Plat Package for SFR at The Bridges Lots 1 -126

Development Package (2nd Review)

DP22-0027



TRANSMITTAL DATE: November 10, 2022



DUE DATE: November 21, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).



Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is February 15, 2023



2-06.3.0 FORMAT REQUIREMENTS



CONTENT REQUIREMENTS



This comment was not addressed correctly. Sheets 16-24 have the wrong case number, DP22-0017 not DP22-0027. COMMENT: 2-06.4.3 – Provide the development package case number, DP22-0027, adjacent to the title block on all sheets.



2-06.4.7 - General Notes

The following general notes are required. Additional notes specific to each plan are required where applicable.



2-06.4.9 - Information on Proposed Development

The following information on the proposed project shall be shown on the drawing or added as notes.



This comment was not addressed. COMMENT: Provide a copy of the Design Review Committee approval letter with the next submittal, see PAD-15 Section C.6.



If you have any questions about this transmittal, please contact Nicholas Ross at Nicholas.Ross@tucsonaz.gov.



RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package