Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE REVIEW v.2
Permit Number - DP22-0010
Review Name: DEVELOPMENT PACKAGE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/09/2023 | Commercial Plumbing | APPROVED | |||
07/13/2023 | NPPO | APPROVED | Previously approved 8/22 | ||
07/13/2023 | Site Landscape | APPROVED | Previously approved 8/22 | ||
08/09/2023 | CDRC Post Review | PENDING ASSIGNMENT | |||
07/28/2023 | Fire New Construction | REQUIRES RESUBMIT | Private hydrants are not permitted. Based on the construction of type of the building (IIB), fully protected with sprinklers, the revised fire flow is less than 1750gpm. IFC 2018 appendix C table C102.1, only requires one hydrant. Questions: patricia.shelton@tucsonaz.gov / 520.837.7082 |
||
07/24/2023 | Site Engineering | REQUIRES RESUBMIT | 1. Show how roof drainage up to the 10-yr storm is directed away from/under adjacent sidewalks through the use of gutters/scuppers (TSM 7-01) Scott Haseman scott.haseman@tucsonaz.gov |
||
07/12/2023 | CDRC Application Completeness | REVIEW COMPLETED | |||
07/13/2023 | CDRC Review Coordinator | REVIEW COMPLETED | No external reviewers nor added. | ||
07/13/2023 | OK to Submit - Zoning | REVIEW COMPLETED |