Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: DP22-0010
Parcel: 13213113C

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.2

Permit Number - DP22-0010
Review Name: DEVELOPMENT PACKAGE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2023 Commercial Plumbing APPROVED
07/13/2023 NPPO APPROVED Previously approved 8/22
07/13/2023 Site Landscape APPROVED Previously approved 8/22
08/09/2023 CDRC Post Review PENDING ASSIGNMENT
07/28/2023 Fire New Construction REQUIRES RESUBMIT Private hydrants are not permitted.
Based on the construction of type of the building (IIB), fully protected with sprinklers, the revised fire flow is less than 1750gpm. IFC 2018 appendix C table C102.1, only requires one hydrant.
Questions: patricia.shelton@tucsonaz.gov / 520.837.7082
07/24/2023 Site Engineering REQUIRES RESUBMIT 1. Show how roof drainage up to the 10-yr storm is directed away from/under adjacent sidewalks through the use of gutters/scuppers (TSM 7-01)

Scott Haseman
scott.haseman@tucsonaz.gov
07/12/2023 CDRC Application Completeness REVIEW COMPLETED
07/13/2023 CDRC Review Coordinator REVIEW COMPLETED No external reviewers nor added.
07/13/2023 OK to Submit - Zoning REVIEW COMPLETED