Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEVELOPMENT PACKAGE REVIEW v.1
Permit Number - DP19-0313
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/23/2023 | CDRC Post Review | PENDING ASSIGNMENT | |||
02/23/2023 | Commercial Plumbing | REQUIRES RESUBMIT | The changes made to the current submittal have resulted in some of the lots being incorrectly shown as needing backwater valves. 1. Lot 44 on sheet 7 (FFE 2794.8’), is downstream of manhole #520 (Rim 2793.11’) does not require a backwater valve. 2. Lot 45 on sheet 7 (FFE 2795.0’), is also downstream of manhole #520 (Rim 2793.11’) and does not require a backwater valve. Reference: Section 714.1, IPC 2018 as amended by the City of Tucson. |
||
01/26/2023 | OK to Submit - Engineering | REVIEW COMPLETED |