Plan Number: CIP-1225-00030
Parcel: Unknown

Address:
501 W 18TH ST

Review Status: In Review

Review Details: CIP - DEV SITE + COMM STRUCTURE - INITIAL v.1

Plan Number - CIP-1225-00030
Review Name: CIP - DEV SITE + COMM STRUCTURE - INITIAL v.1
Review Status: In Review
Review Date Reviewer's Name Type of Review Description Status Comments
Zoning Administration NOT REQUIRED
Zoning Compliance Review NOT REQUIRED
CDRC Post Review Express PENDING ASSIGNMENT
Entitlements PENDING ASSIGNMENT
Real Estate PENDING ASSIGNMENT
Storm to Shade Review PENDING ASSIGNMENT
Commercial Building REQUIRES RESUBMIT ACTIVITY NO. CIP-1225-00030
ADDRESS: (501 W 18TH ST TUCSON, AZ 85701)

Submit your corrected drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Please paste the review comment individually and enter your response directly below it. Please do this for every comment. Review will not proceed without the response letter. Should the above not followed, it may delay your approval. Additionally, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed.


COMMENTS:
1. At time of the actual building permit application submittal, please do make sure to enter the Valuation Value of the project necessary to establish the permit fees.
2. In your Cover Sheet/Front Page, please list the special inspections required for this project IBC 107.2.1 For example, Post installed anchors.
3. Please provide a special inspection certificate with Part A, and Part B completed with next submittal. This form is available in https://www.tucsonaz.gov/files/sharedassets/public/city-services/planning-development-services/documents/special_inspection_certificate.pdf
Ensure that Part B is sealed/signed/dated by the special inspector in charge. Ensure to use Special Inspectors who are active in the approved list of special inspectors. They are available in the following links:
special-inspectors-by-name.pdf (orovalleyaz.gov)
https://content.civicplus.com/api/assets/e426f390-7bd6-4c47-9bc1-357282083afd
https://www.phoenix.gov/pddsite/Documents/TRT/dsd_trt_pdf_00870.pdf
4. Sheet G1.2 Project Description
a. Please enter the proper information.
b. This currently contains instructions as to what to enter.
5. Sheet A6.1, 1-Enlarged Floor Plan - Restroom
i. Shower
1. Grab Bars are missing on the restroom shower drawing.
2. Please correct this.
6. Sheet A6.1, 1-Enlarged Floor Plan – Reception
a. Provide cross section drawing at accessible counter illustrating the following.
i. Knee clearance shall be 11 inches min in depth at 9 inches above the floor, and 8 inches min in depth at 27 inches above the floor. Sec 306.2.4
ii. Additional toe clearance space extending greater than 6 inches beyond the available knee clearance at 9 inches above the floor. Sec 306.3
iii. Knee clearance shall be 30 inches min in width. 904.3.2
7. Sheet A2.1 Floor Plan
a. Storage Racking System
i. Provide Structural Calculation and installation detail drawings of the racking system.
8. Sheet A2.2
a. Accessible Toilet Room
i. Ensure the Circular Turning Space is 67 inches, a new change in the 2024 International Building Code.
9. Sheet A5.2 Detail Drawing 5 Section – Loading Dock
a. The trench drain detail drawing is missing. Please provide this drawing.
b. Please show where the water flow will be routed.
10. Four (4) Water Harvesting Storage Tanks
a. Please submit detail drawings how these tanks are to be installed.
b. Provide tanks foundation detail drawings.
c. Provide mechanism as to how it is filled from the roof and how it is drained.
11. Please resubmit.
Should you have any questions about these comments, I can be reached at Justin.Eder@tucsonaz.gov or 520-837-4976.
Bldg Permits - Post Review Express REVIEW COMPLETED
Building Official REVIEW COMPLETED
Commercial Electrical REVIEW COMPLETED Commercial Electrical Review CIP-1225-00030 (501 W 18TH ST TUCSON, AZ 85701)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

Electrical Review:

Plans shall include (as necessary for scope of work), but may not be limited to items below:
1. Provide an electrical demo plan for any demo’ed electrical or appliances.
2. Provide electrical load calculations, for the Main Panels, Per NEC 220.40, demonstrating the existing electrical system can support the additional load.
3. Show all wiring methods in detail for all new or modified branch circuit conductors and feeders. Conductor type and conduit size/type. Note wet use requirements. NEC arts;300 and 408.4.
4. Provide a panel schedules, showing the circuits that are being modified, added or removed or existing. NEC arts;300 and 408.4. Include panel bus rating and A.I.C. rating. IBC 107.1.
5. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
6. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.
7. Designate the circuit number on the electrical plans, that corresponds to the panel schedule, at the location of each existing, new or modified light fixture, receptacle, and equipment disconnect switch, NEC arts;300 and 408.4. IBC 107.1. Each electrical outlet should be labeled by panel and circuit number.
8. Show all GFCI protection (NEC 210.8(B)) in readily accessible location per NEC 210.8.

Additional comments may be forthcoming with complete electrical plans for the building and site.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
Commercial Mechanical REVIEW COMPLETED ACTIVITY NO. CIP-1225-00030
ADDRESS/PARCEL: (501 W 18TH ST TUCSON, AZ 85701)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Clearly label all equipment and systems on the mechanical plans, including supply CFM, exhaust fans, etc.
2. Please show Exhaust Fan, EF-1, on the mechanical plans.
3. Show the routing of all condensate lines and their termination at the mop sink.
4. The staff restroom/shower area shows no required exhaust ventilation in the outdoor air calculation table. Please revise to reflect the required exhaust ventilation per Section 403.3.1.1 of the 2018 IMC.
Commercial Plumbing REVIEW COMPLETED ACTIVITY NO. CIP-1225-00030
ADDRESS/PARCEL: (501 W 18TH ST TUCSON, AZ 85701)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Revise the site plan to include the following existing utility information:
a. The location and size of all sanitary and storm sewer lines, including pipe diameters and the invert and rim elevations of all manholes and cleanouts, along with the Pima County Wastewater Management Department (PCWMD) reference number.
b. The point of connection to the existing public sewer system.
c. The building first floor elevation (currently shown on the grading plan but not on the site plan).
d. The location and size of the water service lines, clearly identifying what is existing and what is proposed.
2. Roof drains are shown on the site plan, however, scuppers are shown on the roof plan. Please coordinate the drawings and revise the site plan to reflect the roof drainage system shown on the roof plan.
3. The overflow roof drain guard is shown as recessed. Is this correct? Please demonstrate compliance with Section 1102.6 of the 2018 IPC and confirm that both the primary and overflow roof drainage systems are sized for the same capacity.
4. The proposed scuppers appear to be undersized. Section 1106.5 of the 2018 IPC requires parapet wall scuppers to have a width equal to or greater than the circumference of a roof drain sized for the same roof area. Based on the flow rates shown on Sheet A4.1, a 3-inch roof drain would be required per Table 1106.2, which has an approximate circumference of 9.5 inches. Reference: Section 1105.2, 2018 IPC
5. Please show the overflow scuppers on the Roof Plan and Roof Details sheets. Reference: Section 1108, 2018 IPC
6. Provide all construction details for the shower installation and demonstrate compliance with Section 421 of the 2018 IPC.
Fire New Construction REVIEW COMPLETED
New Services/JOC REVIEW COMPLETED No comments at this time. There is no observable impact on the existing potable water distribution main.
NPPO REVIEW COMPLETED SEE SITE LANDSCAPE COMMENTS FOR NPPO COMMENT.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
Outdoor Lighting REVIEW COMPLETED Outdoor Lighting Review CIP-1225-00030 (501 W 18TH ST TUCSON, AZ 85701)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Provide an outdoor site lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your lighting fixture table and use the same number on your site plan.
2. List the Lighting Area per OLC (E3) chapter 3 and used in Table 401.1. Specify the compliance option from Table 401.1 that is being used. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 104.2.1, 401.2. Include all exterior fixtures on the property in the calculations. List shielded and unshielded lights in the calculation.
4. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4.
5. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
6. Fixtures installed under canopies and overhangs. Outdoor lighting fixtures shall not be counted in determining the total light output when they are full cutoff light fixtures installed under canopies, building overhangs, or roof eaves, OLC 401.2.1(3).
7. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf

8. Specify any exceptions used.

9. Provide Curfew lighting controls If applicable Per section 403.

10. Update the lighting schedules on sheet E3.1 to provided unique titles.



Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
ROW Engineering Review REVIEW COMPLETED Add ADA midblock Ramps to Armijo St and 20th St T-intersections.
Driveway should be concrete from curb line to back of sidewalk, cross slope should not exceed 2% in cross walk area.
Add sidewalk width in public ROW.
Close unused curb openings.
Signs REVIEW COMPLETED All signage to be per current code standards and applied for using a separate sign permit application.
Site Engineering REVIEW COMPLETED Permit: CIP-1225-00030
Location: 501 W 18TH ST
Review Date: 12/17/2025

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-6 and Technical Manual (TM) Section for waste management, Pedestrian Access, Hydrology -Retention/Detention Requirements, and all site standard code.

Drainage Manual Link: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/cot-drainage-manual-searchable.pdf
Design standards for Stormwater Detention and Retention Link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/engineering-code/updated-retention-detention-manual.pdf

Site Engineering Comments:
1. As acres of disturbance Is greater than one acre, a Storm water pollution prevention plan will be required as well as a dust control permit.
2. A Drainage report will be required to show full compliance with first flush retention/balanced basin detention requirements. Refer to the Design standards for Stormwater Detention and Retention Chapters 2, 3, & 4. Drainage report content and format requirements can be found in chapter 10 of the DSSDR as well.
3. As the parcel has the 18th ST wash run along the West portion of the property, as well as the main development falling within the City of Tucson Downtown Airport Wash floodplain, it will be required that the floodplain limits (If any) be shown/called-out on the site plan.
4. A floodplain use (FPU) permit will be required to be submitted with the development package to cover the site work proposed. A FPU permit with elevation certificate will also be required for the associated commercial building permit.
5. Wheel stops will be required at all parking spaces adjacent to the sidewalks so as not to reduce the sidewalk path to less than 4 feet. UDC 7.4.6 Sidewalks that are 6 and a half feet or wider will not require adjacent parking spaces to have wheel stops
6. Show that erosion protection is used for all inlet and outlet structures. The erosion protection shall extend below the finished grade of the basin floor and/or side slope to the appropriate design depth. DSSDR 4.8.1.4 Show this for all inlet structures
7. Provide a descriptor box adjacent to each basin on the grading plan (Includes Stormwater Harvesting basins/landscaping). Include a leader arrow to the basin or provide a label for the basin and reference the label on the top of the descriptor box. Include the following applicable information in the descriptor box: a. Total volume, cubic feet or acre feet; b. If applicable, detention volume, cubic feet or acre feet; c. If applicable, retention volume, cubic feet; d. If applicable, first-flush retention volume, cubic feet; e. If applicable, Q100 in, cubic feet per second; f. If applicable, Q100 out, cubic feet per second; g. Basin top elevation, feet; h. 100-year water surface elevation, feet; and i. 100-year ponding depth, (measured from the lowest elevation of the basin), feet. DSSDR 11.1.3
8. Revise the trash enclosure on grading plan to show the ramps slope being 2% away from enclosure as well as the enclosure slab sloping 1% to the gate. TSM 8-1.0.0
9. Sheet 24 provides keynote # 102 “8’ tall wall,” As this is greater than 7-feet, it will require that a separate structural wall permit with structural calculations/drawings be submitted for construction of the wall.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
Site Landscape REVIEW COMPLETED PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: NEW WAREHOUSE BUILDING ON THE SOUTH SIDE OF TUCSON WATER PLANT 1
ACTIVITY NO: CIP-1225-00030
ADDRESS: 501 W 18TH ST
ZONING: C-3; R-2; I-1
12.22.2025

THE PROPOSED PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH APPLICABLE DEVELOPMENT STANDARDS PER THE CITY OF TUCSON UNIFIED DEVELOPMENT CODE (UDC), TECHNICAL STANDARDS MANUAL (TSM), AND ADMINISTRATIVE MANUAL (AM) FOR SITE LANDSCAPE, NATIVE PLANTS, AND RAINWATER HARVESTING.

RESUBMIT REVISED DRAWINGS ALONG WITH A DETAILED RESPONSE LETTER, STATING HOW ALL OF THE SITE LANDSCAPE AND NPPO SECTION REVIEW COMMENTS HAVE BEEN ADDRESSED.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. Provide a summary of required and provided plant material for landscape borders and for parking lot canopy trees per the Unified Development Code.

2. Provide a Commercial Rainwater Harvesting plan per the Technical Standards Manual. Ensure that the rainwater harvesting plan and the grading plan are complete and coordinated.

3. It is understood that the plans are preliminary as part of the Capital Improvement Project process. Provide all pertinent plans, details, and general notes required to complete construction of the site landscape.

4. The site may have protected native plants growing on site. Provide documentation from your native plant professional that native plants have been inventoried and include a NPPO or a NPPO Waiver, whichever is applicable to this site.

Thank you.
Chad Keller, RLA
Landscape Architect
chad.keller@tucsonaz.gov
Site Zoning REVIEW COMPLETED FROM: Ramiro Olivarez
PDSD Zoning Review Section
PROJECT: CIP-1225-00030
501 W 18TH ST
Tucson Water Plant 1 - AE P24025 New Warehouse Building (Intermediate Review)
TRANSMITTAL DATE: ‎January 09, 2026

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)
Section

1. Comment: Provide the development package case number, CIP-1225-00030, adjacent to the title block on each sheet.

2. For the next review of this CIP please separate the development package (dp) sheets from the building plans.

3. Comment: An index of sheets in the development package shall be provided on the first sheet.

4. Comment: If applicable, include the administrative street address and relevant case numbers (development package document, subdivision, rezoning, board of adjustment, DDO, MDR, DSMR, overlay, etc.) shall be provided adjacent to the title block on each sheet.

5. Comment: List the applicable rezoning file number and conditions of approval. Also place the C9-__-__ (if applicable) and the plan/plat file numbers in the lower right corner of each sheet.

6. Comment: Identify the existing and proposed use of the property as classified per the UDC. List all UDC sections applicable to the proposed uses.

7. Comment: If a plan or plat is prepared in conjunction with other applications or overlays or the parcel being developed is subject to conditions of an application processed previously, additional information must be added to the plan. Such applications and overlays include, but are not limited to: annexations; rezonings; special exceptions; Board of Adjustment variances; Design Development Options; Technical Standard Modification Request; overlays (Airport Environs Zone, Environmental Resource Zone, Gateway Corridor Zone, Hillside Development Zone, Historic Preservation Zone, Major Streets and Routes, Rio Nuevo District, Scenic Corridor Zone, WASH); Modification of Development Regulations through the Downtown Area Infill Incentive District or Rio Nuevo District; Downtown Heritage Incentive Zone; or, Design Review Board. Provide the following information on the plan.

If applicable, list additional applications and overlays, by case number.

8. Comment: If applicable, List additional applications and overlays, by case number (if applicable), in lower right corner of each sheet. As a general note provide the type of application processed or overlays applicable, a statement that the project meets the criteria/conditions of the additional application or overlay, the case number, date of approval, what was approved, and the conditions of approval, if any.

9. Comment: As this site is made up of multiple parcels, a Tax Parcel Combination is required. Provide the approved lot combination request form. If the proposed development does not meet this requirement, provide a City Manager Waiver in accordance with Section V of the Administrative Directive 1.07-6 with the formal Development Package.

10. Comment: In the general notes list the –

Floor area for each building;

Percentage and area in square feet of building and accessory building coverage;

Percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and

When the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met.


11. Comment: Provide site boundary/subdivision perimeter information, including bearing in degrees, minutes, and seconds, with basis for bearing noted, together with distances in feet, to hundredths of a foot, or other functional reference system.

12. Comment: If applicable, all easements shall be drawn on the plan. The recordation information, location, width, and purpose of all easements on site will be stated. Blanket easements should be listed in the notes, together with recordation data and their proposed status. Should an easement not be in use and be proposed for vacation or have been abandoned, so indicate. However, should the easement be in conflict with any proposed building location, vacation of the easement shall occur prior to approval of plan unless written permission from easement holder(s) is provided.

13. Comment: The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

14. Comment: All existing zoning classifications on and adjacent to the project (including across any adjacent right-of-way) shall be indicated on the drawing with zoning boundaries clearly defined. If the property is being rezoned, use those boundaries and classifications. The basis for this requirement is that some zoning requirements on a project are based on the zoning classification of adjacent property. Also, in some instances, each zone has to be taken into consideration on property that is split by two or more zoning classifications, as each may have different requirements.

15. Comment: Indicate if existing streets are public or private; provide street names, widths, curbs, sidewalks, and utility locations, all fully dimensioned.

16. Comment: If utilizing parking area access lanes (PAALs), they shall be designed in accordance with Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

17. Comment: Show all motor vehicle off-street parking spaces provided, fully dimensioned. As a note, provide calculations on the number of spaces required (include the ratio used) and the number provided, including the number of spaces required and provided for the physically disabled. The drawing should indicate parking space locations for the physically disabled. A typical parking space detail shall be provided for both standard parking spaces and those for the physically disabled. For information on parking requirements for the physically disabled, refer to adopted building and accessibility codes of the City of Tucson. Design criteria for parking spaces and access are located in Section 7.4.6, Motor Vehicle Use Area Design Criteria, of the UDC.

18. Comment: Show bicycle parking facilities fully dimensioned. For specifics, refer to Section 7.4.9, Bicycle Parking Design Criteria, of the UDC. Provide, as a note, calculations for short and long term bicycle spaces required and provided.

19. Comment: If applicable, all proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval.


20. Comment: See Site Landscape review comments as it pertains to the following:

A conceptual grading plan is required on projects with significant topographic conditions. The PDSD Engineering Administrator or designee will determine the need for such a plan.

Concurrent Reviews - For all projects, grading plans may be included in the development package and will be reviewed concurrently.

21. Comment: Draw, label, and dimension all applicable building setback lines, future right-of-way building setback lines and setback lines such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

22. Comment: Show refuse collection areas, including locations of dumpsters, screening location and materials, and vehicle maneuverability, fully dimensioned, and access route. If dumpster service is not proposed, indicate type of service. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

23. Comment: For gang mailboxes indicate location to assure there are no conflicts with other requirements, such as pedestrian accessibility, utilities, and landscaping. Indicate with a general note if mail is to be delivered to the proposed building.

24. Comment: If applicable, indicate the locations and types of proposed signs (wall, free-standing, pedestal) to assure there are no conflicts with other requirements and that minimal locational requirements can be met. Indicate if there are any existing billboards on site. Compliance to the Sign Code, Chapter 3 of the Tucson Code, is required.

25. Comment: See Site Landscape review comments as it pertains to the following: show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-11.0.0, Landscape Plan Requirements.

26. Comment: Additional comments may be forthcoming on the next review based on the proposed use and applicable use specific standards

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected CIP.
If you have any questions about this transmittal, please contact Ramiro.Olivarez@tucsonaz.gov
Traffic Engineering Review REVIEW COMPLETED No comments
TSMR/PDMR - Engineering REVIEW COMPLETED
TW New Development Review REVIEW COMPLETED No comments at this time. There is no observable impact on the existing potable water distribution main.
TW Planning and Engineering Review REVIEW COMPLETED This project was initiated in-house and internally reviewed. No comments at this time.
Water - PDSD REVIEW COMPLETED ACTIVITY NO. CIP-1225-00030
ADDRESS/PARCEL: (501 W 18TH ST TUCSON, AZ 85701)
Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.
COMMENTS:
1. Provide the size, routing, and material of the water service to the proposed building, along with an estimate of the total water demand served by the water meter. Also show the size and location of the backflow preventer. Reference: Section 603.1, 2018 IPC
Zoning Modifications - DDO REVIEW COMPLETED
Zoning Modifications - IPP REVIEW COMPLETED
Zoning Modifications - MS&R REVIEW COMPLETED
Zoning Modifications - Variance REVIEW COMPLETED