Plan Number: CIP-1225-00029
Parcel: 11519004S

Review Status: Requires Resubmit

Review Details: CIP - DEV SITE + COMM STRUCTURE - FINAL v.2

Plan Number - CIP-1225-00029
Review Name: CIP - DEV SITE + COMM STRUCTURE - FINAL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Site Engineering APPROVED
CDRC Post Review Express REQUIRES RESUBMIT Please address reviewers comments for the next submittal.
Bldg Permits - Post Review Express REVIEW COMPLETED
Commercial Building REVIEW COMPLETED
Outdoor Lighting REVIEW COMPLETED Outdoor Lighting Review CIP-1225-00029 (2102 N DRAGOON ST TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2024 International Building Code (IBC), 2023 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov

1. Submitted plans are missing the required Lumen Calculations showing the new/replacement lights and existing lights meet the maximum lumen totals of Table 401.1.
>>> Sheet EL210 has photometric data for the new/replacement lights. (Not required for the existing lights.)
>>> Sheet E-701 has the luminaire schedule showing the new/replacement lights meet color temperature and shielding requirements. And provides lumen totals for each fixture, F, FE.
>>> Only thing missing is updated Lumen Calculations as required.


OLC 104.2.1 Lumen calculation on plans. There shall be documentation on the plans to demonstrate compliance with the lumen cap per Table 401.1, and which includes the following information:
1. Each exterior luminaire type with the lumens for that type, the quantity of each type and whether the luminaire is full cut-off or unshielded.
2. The total of full cut-off and unshielded lumens for the parcel.
3. A statement of the lighting area, the size of the permitted parcel, and the maximum allowed full cut-off and unshielded lumens.

OLC 104.2 Permit submission requirements. The applicant for any permit required by any provision of the laws of this jurisdiction in connection with proposed work involving outdoor lighting fixtures shall submit (as part of the application for permit) evidence that the proposed work will comply with this code.
PDSD Application Completeness Express REVIEW COMPLETED
TW Planning and Engineering Review REVIEW COMPLETED