Review Status: Approved

Review Details: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1

Plan Number - CIP-1224-00037
Review Name: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Real Estate NOT REQUIRED Any proposed improvements located outside property lines and into public rights-of-way require a right-of-way permit and Private Improvement Agreement with the Department of Transportation & Mobility or Temporary Revocable Easement with the Real Estate Division (separate processes). If any action is required to address property rights (dedications, easements, etc), please contact the Real Estate Division 520-791-4181.
Zoning Administration NOT REQUIRED
Bldg Permits - Post Review Express REVIEW COMPLETED
CDRC Post Review Express REVIEW COMPLETED Please address all reviewers' comments. Once plans are between 90-100% external reviewers can be added. Please fill out all information in the additional info screen. Please review notes about the possible dust permit needed. Thanks
Commercial Building REVIEW COMPLETED
Commercial Electrical REVIEW COMPLETED Commercial Electrical Review CIP-1224-00037 (2700 E LA MADERA DR TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Show or Note that all applicable electrical work shall comply with, Corrosive Environment – NEC 680.7, 680.14. REF Sheet E5.2, Electrical Plan – Splash Pad Equipment Room.
2. Provide Equipotential Bonding per 680.26. the splashpad shell, reinforcing steel, perimeter surfaces, metallic components, fixed metal parts, etc., shall be bonded per 680.26.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
Commercial Mechanical REVIEW COMPLETED
Commercial Plumbing REVIEW COMPLETED 1. Provide backflow protection for the potable water supply to the splash pad equipment enclosure. Reference: Section 608.1, IPC 2018.
2. The specified freeze-proof yard hydrant (Keynote 7, Utility Plan) utilizes a below-grade drain and is therefore unacceptable for potable water. Reference: Section 608.8, IPC 2018.
3. Revise keynote 15 on the Utility Plan, to call for the replacement of all piping in the existing restroom/concession building that had been used for non-potable water. Reference: Section 608.11, IPC 2018.
Entitlements REVIEW COMPLETED
Fire New Construction REVIEW COMPLETED Shade materials shall comply with Chapter 31 of the 2024 International Fire Code and NFPA 701.
New Services/JOC REVIEW COMPLETED NAD will not allow potable water to be delivered to piping that was used for reclaimed water. The 2018 IPC prohibits piping that has been used for non-potable water to be re-used for potable water.
Outdoor Lighting REVIEW COMPLETED Outdoor Lighting Review CIP-1224-00037 (2700 E LA MADERA DR TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. Clarify why the existing basketball court lights are not included in the lumens calculation.
2. Provide Curfew lighting controls If applicable Per section 403.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
ROW Engineering Review REVIEW COMPLETED No improvements in the RoW
Site Engineering REVIEW COMPLETED
Site Landscape REVIEW COMPLETED
Site Zoning REVIEW COMPLETED
Storm to Shade Review REVIEW COMPLETED No comments
TW Planning and Engineering Review REVIEW COMPLETED Previous Comments have been addressed. P&E has no other objections.
Water - PDSD REVIEW COMPLETED