Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: CIP-1124-00036
Parcel: 115080950

Review Status: Requires Resubmit

Review Details: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1

Plan Number - CIP-1124-00036
Review Name: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Transportation Landscape Review APPROVED
Building Official NOT REQUIRED Building Official review is not necessary at this time. Commercial building review will identify when potential building code appeals may be needed.
Neighborhood Traffic Mitigation NOT REQUIRED
NPPO NOT REQUIRED
Zoning Administration NOT REQUIRED
Zoning Compliance Review NOT REQUIRED
CDRC Post Review Express REQUIRES RESUBMIT Please resubmit and address all reviewers' comments.
Please fill out the additional info screen with total site acres and acres of disturbance. If acres of disturbance is greater than 1 acre, a dust permit may be required.
Historic REQUIRES RESUBMIT Continuing consultation for Section 106 required. PRS review scheduled for 9/25/25.
Bldg Permits - Post Review Express REVIEW COMPLETED
CDRC Application Completeness Express REVIEW COMPLETED
Commercial Building REVIEW COMPLETED 1. Please amend plans to identify the fire-resistance rating of all walls, floors and elements on each floor’s plan view. IBC 602.1 Alternatively provide separate sheets with this information included.
2. Please amend plans to provide a reference for where to find the construction information for the fire-rated assemblies. IBC 703.3
3. Please amend plans to indicate balconies/decks are fire-rated or meet another option. If sprinklers extend to balconies, that requirement is stated on the cover or code data sheet where the sprinkler type is called out. IBC 705.2.3.1
4. Please amend plans to provide details for penetration firestops. The entire assembly is shown in the drawings. IBC 714.1 For example, if putty pads are used with the electrical box installation please show on the plans. Amend plans to indicate the penetrations in walls and floors are identified with a reference where to find information. IBC 714.1
6. Sheet a1.1: Please amend plans to label all accessible rooms and the accessibly TYPE on floor plan for consistency IBC 107.2.1
7. Please amend plans to show a photometric plan or other method of showing 1 footcandle of normal power illumination at the walking surface along the path(s) of exit discharge, while the building is occupied. IBC 1008.2.1, IBC 1008.2.3
8. Sheet S1.1: Please amend plans to list the required special inspections and provide a project specific statement of special inspections. IBC 107.2.1 & 1704.1
9. Sheet a3.0: Please amend plans to indicate the type and location of the roof vents and list the effective net free area of the roof vent system. IBC 107.2.1
10. Please amend plans to show the method of roof access for roofs over 16 feet high with equipment, a permanent ladder is provided. IMC 306.5
11. During our discussions the replacement of stairs with cracked or non-uniform treads and risers was discussed. Is this indicated on the drawings? Please indicate where this information is included in these drawings. IBC 107.2.1
12. If any of the following items are being totally reconstructed, where balconies or other elevated walking surfaces are exposed to water from direct or blowing rain, snow, or irrigation, and the structural framing is protected by an impervious moisture barrier, the construction documents shall include details for all elements of the impervious moisture barrier system. The construction documents shall include manufacturer’s installation instructions. 107.2.5
13. Structural Calculations: Pleases amend the calculations to add a footing key plan and footing schedule within the calculations. IBC 107.2.7
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
Commercial Electrical REVIEW COMPLETED Commercial Electrical Review CIP-1124-00036 (1136 N STONE AV TUCSON, AZ 85705)
90% Review:


1. Show electrical outlets, panels and other penetrations within fire-rated walls with 1-hr fire ratings. IBC 714. The rooms are required to have 1-hour separation, both vertically and horizontally. They can be reduced to 30 min separation when sprinkled. See also Commercial Building Review Comments.
Commercial Mechanical REVIEW COMPLETED
Commercial Plumbing REVIEW COMPLETED Show how the supply piping to each dwelling unit complies to Section 606.1 (6), IPC 2018.
Entitlements REVIEW COMPLETED
External Reviewers - Southwest Gas REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
External Reviewers - Tucson Electric Power (TEP) REVIEW COMPLETED TEP Approved at 90%
Fire New Construction REVIEW COMPLETED Maintain Fire Department access in accordance with IFC 2024, 503.2 and local amendments. Provide fire sprinklers in accordance with IFC 2024, 903.3.1.2. Provide fire alarms as required in IFC 2024, 907.2.9, & 903.4.1.
Questions: patricia.shelton@tucsonaz.gov
New Services/JOC REVIEW COMPLETED TUCSON WATER NEW AREA DEVELOPMENT HAS NO OBJECTION TO THE RENOVATION OF THE BUILDING. THE PARCEL IS SERVED BY A 2" WATER METER CONNECTED TO THE 8" PVC WATER MAIN IN WEST NORTH STONE. PLEASE ENSURE THAT THE WATER METER IS LOCATED A MINIMUM OF 8 FEET AWAY FROM THE BUILDING IN ACCORDANCE WITH TUCSON WATER STANDARDS. IF ANY NEW WATER SERVICES OR IRRIGATION METERS ARE NEEDED, CONTACT TUCSON WATER NEW SERVICES TO REQUEST THOSE SERVICES.
Outdoor Lighting REVIEW COMPLETED No comments.
PDSD Application Completeness Express REVIEW COMPLETED
Real Estate REVIEW COMPLETED If any issues related to property rights or encroachments into RoW emerge, please contact the RE Division.
ROW Engineering Review REVIEW COMPLETED ADA ramps should line crossing the Alley on Helen St.
DTM Comment File has been added to attachments.
ROW permit required prior to working in the ROW
Signs REVIEW COMPLETED
Site Engineering REVIEW COMPLETED Permit: CIP-1124-00036
Location: 1136 N STONE AV
Review Date: 9/8/2025
Site Engineering Comments:
1. Previous comments not addressed: 1. A portion of this building is within a City of Tucson regulatory floodplain (Mabel Street Floodplain). A floodplain use permit is required. Please provide a PDF cost estimate for materials and labor for the floodplain use permit.
2. Stone Ave is classified as an Arterial Road, revise Sight visibility triangles accordingly in compliance with TSM 10-01.5.3
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
Site Landscape REVIEW COMPLETED CDRC TRANSMITTAL
PLANNING AND DEVELOPMENT SERVICES DEPARTMENT
REVIEWER: CHAD KELLER, RLA
PDSD SITE LANDSCAPE/NATIVE PLANT PRESERVATION SECTION

PROJECT: TO REHAB A 51 UNIT MOTEL CONVERTING THEM INTO KITCHENETTES. SITE TO HAVE UPGRADES IN ELECTRICAL, MECHANICAL, AND PLUMBING (CITY OWNED PARCEL)
ACTIVITY NO: CIP-1124-00036
ADDRESS: 1136 N STONE AV
ZONING: C-3 COMMERCIAL ZONE
LAND USE: CHANGE OF USE (FULL LANDSCAPE CODE COMPLIANCE)
REVIEW 3

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants, and water harvesting.

Please resubmit revised drawings along with a detailed response letter, which states how all Landscape/NPPO Review Section comments are addressed.

SITE LANDSCAPE/NPPO SECTION COMMENTS:

1. Provide a City Manager Waiver for the following (two) site landscape requirements with the 100 percent plan set resubmittal.

a. Street landscape border along N Stone Av and along E Helen St. per UDC 7.6.4.C-2 and Table 7.6.4-1.

b. Trees in all vehicular parking areas (1 tree to 4 parking spaces) per UDC 7.6.4.B.1.

2. All site landscape and screening standards per (UDC 7.6.4) for street landscape borders and parking lot trees that cannot be met shall provide a City Manager Waiver in accordance with Section V of the Administrative Directive 1.07-6 prior to development package approval.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
520.837.4923
Site Zoning REVIEW COMPLETED CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Ramiro Olivarez
PDSD Zoning Review Section

PROJECT: Conversion of motel to multifamily development
Capital Improvements Project (CIP) – Final
CIP-1124-00036 (1136 N STONE AV TUCSON, AZ 85705)


TRANSMITTAL DATE: September 23, 2025
DUE DATE: September 12, 2025

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


SECTION 2-06.0.0: DEVELOPMENT PACKAGE (TENTATIVE PLATS AND SITE PLANS)


1. COMMENT: 2-06.4.1 – Provide the name, mailing address, and email addresses, and phone number of the primary property owner of the site, and the developer of the project.

2. PREVIOUS COMMENT 2 WAS NOT ADDRESSED: 2-06.4.7.A.6 – Correct the Zoning and Land Use Note #16 stating “this project is designed to meet the overlay zone(s) criteria. UDC Article 5.4 Major Streets and Routes Setback Zone (MS&R).

3. PREVIOUS COMMENT 3 WAS NOT ADDRESSED: 2-06.4.9.H.5.a – It appears the proposed development is not meeting the minimum parking requirement. The proposed development includes 49 units and requires 1 space per unit, which results in a minimum requirement of 49 parking spaces. The development proposes 12 on-site parking spaces. To reduce the parking requirement, provide a City Manager Waiver in accordance with Section V of the Administrative Directive 1.07-6 with the formal Development Package submittal.

FOLLOW UP TO COMMENT 3: Comment 3 will remain until a formal City Manager Waiver is provided.

4. PREVIOUS COMMENT 4 NOT ADDRESSED: 2-06.4.9.H.5.d – The minimum required parking ratio for long-term bicycle parking is 0.5 spaces per bedroom. If the proposed development does not meet this requirement, provide a City Manager Waiver in accordance with Section V of the Administrative Directive 1.07-6 with the formal Development Package.

FOLLOW UP TO COMMENT 4: Comment 4 will remain until a formal City Manager Waiver is provided.

5. PREVIOUS COMMENT 5 NOT ADDRESSED: 2-06.4.9.R – Clearly demonstrate the trash enclosure is connected by an ADA compliant pedestrian circulation path.

6. PREVIOUS COMMENT: 2-06.4.9.T – Please consult with Environmental Services regarding the design and location of the refuse collection areas.

FOLLOW UP TO COMMENT 6: Contact Andy Vera for any proposed modifications to trash enclosures or Environment Services trash collection standards.

7. PREVIOUS COMMENT 7 NOT ADDRESSED: 2-06.4.9.V – Clarify if there will be gang mailboxes and demonstrate the location, if applicable.

FOLLOW UP TO COMMENT 7: If applicable, in the zoning & land use notes indicate if there will be gang mailboxes.

***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Ramiro Olivarez by email Ramiro.Olivarez@tucsonaz.gov


***For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations


If you have any questions about this transmittal, Contact Ramiro Olivarez by email Ramiro.Olivarez@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and comment response letter. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home.
Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf
TSMR/PDMR - Engineering REVIEW COMPLETED
TSMR/PDMR - Environmental Services REVIEW COMPLETED Contact Andy Vera for any proposed modifications to trash enclosures or Environment Services trash collection standards.
TSMR/PDMR - Landscape REVIEW COMPLETED
TSMR/PDMR - Zoning REVIEW COMPLETED
TW Planning and Engineering Review REVIEW COMPLETED No comments to provide at this time. There is no observable impact on the existing water distribution system. There is no observable change in the existing demand for water. If there is a need for new service or irrigation meters please contact New Services
If there are any changes in the future or questions please contact michael.asbury@tucsonaz.gov
Water - PDSD REVIEW COMPLETED
Zoning Modifications - DDO REVIEW COMPLETED
Zoning Modifications - IPP REVIEW COMPLETED
Zoning Modifications - MS&R REVIEW COMPLETED
Zoning Modifications - Variance REVIEW COMPLETED