Review Status: Requires Resubmit

Review Details: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1

Plan Number - CIP-0525-00009
Review Name: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Site Engineering APPROVED
Site Landscape APPROVED
TW Planning and Engineering Review APPROVED Update well name on LS202 to WR-052
NPPO NOT REQUIRED
CDRC Post Review Express REQUIRES RESUBMIT Please address reviewers comments for the next review.
External Reviewers - Tucson Electric Power (TEP) REQUIRES RESUBMIT 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702
February 24, 2026
WO#T173595
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: MITCHELL PARK IMPROVEMENTS
CIP-0525-00009
Tucson Electric Power Company (TEP) has reviewed and cannot approve the
development plan submitted 1/8/2026. There are existing facilities within the
development which are depicted upon the plan. COMMENTS ONLY PLEASE
INDICATE APPROVAL WITH THE BELOW CHECK BOX PLEASE DO NOT ADJUST
IF THERE ARE NO COMMENTS Further: Public Utility Easement not shown on
development plans
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Chuck Leon
(520) 400-6133
cleon@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
Bldg Permits - Post Review Express REVIEW COMPLETED
CDRC Application Completeness Express REVIEW COMPLETED
Commercial Building REVIEW COMPLETED
PDSD Application Completeness Express REVIEW COMPLETED
Site Zoning REVIEW COMPLETED FROM: Ramiro Olivarez
PDSD Zoning Review Section
PROJECT: CIP-0525-00009
1100 E MITCHELL ST
Mitchell Park Improvements – New ramada Capital Improvements Project (CIP) (Final Review)
TRANSMITTAL DATE: ‎January 22, 2026

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. PREVIOUS COMMENT 1: Provide a Development Package that meets the requirements of the following Checklist for Minor Changes to Existing Commercial Sites - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf

PREVIOUS FOLLOW UP TO PREVIOUS COMMENT 1: Include the information below.

A small, project-location map shall be provided in the upper right corner of the cover sheet. This map shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information;

a. Show the subject property approximately centered within the one square
mile area. Identify major streets within the square mile area and all streets
that abut the subject property. Section, township, and range, north arrow,
and the scale will be labeled.


FOLLOW UP TO PREVIOUS COMMENT 1: Section, township, and range, north arrow,
and the scale will be labeled on the project-location map.


2. PREVIOUS COMMENT STILL APPLICABLE: Include a legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

3. PREVIOUS COMMENT STILL APPLICABLE: Include a title block with a brief legal description.

4. PREVIOUS COMMENT 4: Include the sheet names on each sheet title block.

FOLLOW UP TO PREVIOUS COMMENT 4: Include the sheet Titles on each sheet title block for sheets 8 through 13. Correct Sheet 2 title to match sheet 2 title listed in the sheet index.

5. PREVIOUS COMMENT NOT ADDRESSED: Include a project-location map on the first sheet of the development package in the upper right cover, covering approximately one square mile, drawn at a minimum scale of three inch equal to one mile with the subject property approximately centered within the one square mile area. Include the section, township, and range; section corners north arrow, and the scale labeled.

6. PREVIOUS COMMENT NOT ADDRESSED: Identify all existing zoning classifications on and adjacent to the project (including across any adjacent right of way).

All existing zoning classifications on and adjacent to the project (including across
any adjacent right-of-way) shall be indicated on the drawing with zoning
boundaries clearly defined.

Include the adjacent zoning on the site plan. Or provide a zoning detail of the adjacent zoning (as found on the on the sample plot plan requirements document: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements_dtm-comments.pdf)

7. PREVIOUS COMMENT NOT ADDRESSED: Provide site boundary information, including bearing in degrees, minutes, and seconds, together with distances in feet, to hundredths of a foot, or other functional reference system.

8. PREVIOUS COMMENT NOT ADDRESSED: The following information regarding existing private or public right-of-way
adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

9. PREVIOUS COMMENT NOT ADDRESSED: All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

10. PREVIOUS COMMENT NOT ADDRESSED: Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

Draw, label, and dimension setback lines to the structures. Include setback, maximum height, and total lot coverage calculations (max is 60%) information on the cover sheet.

11. PREVIOUS COMMENT NOT ADDRESSED: Clearly Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

12. PREVIOUS COMMENT NOT ADDRESSED: If applicable, Show refuse collection areas, including locations of dumpsters, screening location and materials. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

13. Comment: Additional comments may be forthcoming on the next review based on the proposed use.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected CIP development package.
If you have any questions about this transmittal, please contact at Ramiro.Olivarez@tucsonaz.gov
Storm to Shade Review REVIEW COMPLETED Review complete, comment response satisfactory