Review Status: Requires Resubmit

Review Details: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1

Plan Number - CIP-0525-00009
Review Name: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Zoning Administration NOT REQUIRED
External Reviewers - Tucson Electric Power (TEP) REQUIRES RESUBMIT 4350 E. Irvington Road
Post Office Box 711, Tucson, AZ 85702
October 22, 2025
WO#T164323
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: Mitchell Park Improvements
CIP-0525-00009
Tucson Electric Power Company (TEP) has reviewed and cannot approve the
development plan submitted 9/24/2025. There are no existing facilities within the
development.COMMENTS ONLY PLEASE INDICATE APPROVAL WITH THE BELOW
CHECK BOX PLEASE DO NOT ADJUST IF THERE ARE NO COMMENTS Further:
TEP Facilities/Public Utility Easement are not shown on Development plan.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Churck Leon
(520)
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
Historic REQUIRES RESUBMIT Mitchell Park is over 50 years old and the Plans Review Subcommittee of the Tucson-Pima County Historical Commission has identified historical-period structure(s) within the park. While no demolitions will be conducted as part of this project, a courtesy review of the plans for the subcommittee is necessary.
Bldg Permits - Post Review Express REVIEW COMPLETED
CDRC Post Review Express REVIEW COMPLETED Please addres akk reviewers comments for the final review.
Commercial Building REVIEW COMPLETED Is there going to be utilities installed such as electrical and lights being installed?
External Reviewers - COT Parks & Recreation REVIEW COMPLETED Approved



Regarding CIP-0525-0009, The City of Tucson Parks and Recreation Department has no additional requirements for the Project and no further reviews by TPRD are required.



Description: : New ramada to provide shade + landscape enhancements (turf reduction, irrigation improvements, trees, shrubs) + Mitchell Park

Parcel: 113094880



Regards,



Joe Barr

Project Manager

Tucson Parks and Recreation
External Reviewers - Southwest Gas REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
External Reviewers - Southwest Gas REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
External Reviewers - United States Postal Service (USPS) REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
ROW Engineering Review REVIEW COMPLETED No Impact to ROW
Site Engineering REVIEW COMPLETED
Site Landscape REVIEW COMPLETED
Site Zoning REVIEW COMPLETED FROM: Ramiro Olivarez
PDSD Zoning Review Section
PROJECT: CIP-0525-00009
1100 E MITCHELL ST
Mitchell Park Improvements – New ramada Capital Improvements Project (CIP) (Intermediate Review)
TRANSMITTAL DATE: ‎October 21, 2025

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. PREVIOUS COMMENT 1: Provide a Development Package that meets the requirements of the following Checklist for Minor Changes to Existing Commercial Sites - https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf

FOLLOW UP TO PREVIOUS COMMENT 1: Include the information below.

A small, project-location map shall be provided in the upper right corner of the cover sheet. This map shall cover approximately one square mile, be drawn at a minimum scale of three inch equals one mile, and provide the following information;

a. Show the subject property approximately centered within the one square
mile area. Identify major streets within the square mile area and all streets
that abut the subject property. Section, township, and range, north arrow,
and the scale will be labeled.

2. PREVIOUS COMMENT NOT FULLY ADDRESSED: Include the name, mailing and email addresses and phone number of the primary property owner of the site, the developer of the project, registrant(s), and other person(s), firm(s), or organization(s) that prepared the development package documents on the cover sheet in the upper right half.

3. COMMENT: Include a legend that shows and describes all symbols used on the drawing is to be provided, preferably on the first sheet.

4. COMMENT: Include a title block with a brief legal description.

5. COMMENT: Include the sheet names on each sheet title block.

6. PREVIOUS COMMENT NOT ADDRESSED: Include a project-location map on the first sheet of the development package in the upper right cover, covering approximately one square mile, drawn at a minimum scale of three inch equal to one mile with the subject property approximately centered within the one square mile area. Include the section, township, and range; section corners north arrow, and the scale labeled.

7. COMMENT: Identify all existing zoning classifications on and adjacent to the project (including across any adjacent right of way).

All existing zoning classifications on and adjacent to the project (including across
any adjacent right-of-way) shall be indicated on the drawing with zoning
boundaries clearly defined.

Include the adjacent zoning on the site plan. Or provide a zoning detail of the adjacent zoning (as found on the on the sample plot plan requirements document: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements_dtm-comments.pdf)

8. PREVIOUS COMMENT NOT ADDRESSED: Include a general note: “Existing zoning is R-2”

FOLLOW UP TO PREVIOUS COMMENT 8: Correct general note 1 existing zoning to “R-2”.

9. PREVIOUS COMMENT NOT ADDRESSED: List the gross area of the site by square footage and acreage.

FOLLOW UP TO PREVIOUS COMMENT 9: Ensure the total project site area is correct.

10. Comment: Upon formal submittal provide the development package case number adjacent to the title block on each sheet.

11. Comment: If applicable, the proposed site is part of a larger site, the calculations encompass the entire site, whether existing or proposed. If the project is being phased, calculations must show that, at each phase, requirements are being met.

12. Comment: Provide site boundary information, including bearing in degrees, minutes, and seconds, together with distances in feet, to hundredths of a foot, or other functional reference system.

13. Comment: The following information regarding existing private or public right-of-way adjacent to or within the site shall be provided: the name, right-of-way width, recordation data, type and dimensioned width of paving, curbs, curb cuts, and sidewalks.

14. Comment: If applicable, All proposed easements (utility, sewer, drainage, access, etc.) are to be dimensioned and labeled as to their purposes and whether they will be public or private. The easements may have to be recorded and the recordation information added to the development package prior to approval.

15. Comment: All applicable building setback lines, such as erosion hazard, floodplain detention/retention basins, and zoning, including sight visibility triangles, will be shown.

16. Comment: Provide the square footage and the height of each commercial, industrial, or business structure and the specific use proposed within the footprint of the building(s).

Draw, label, and dimension setback lines to the structures. Include setback, maximum height, and total lot coverage calculations (max is 60%) information on the cover sheet.

17. Comment: Clearly Show on-site pedestrian circulation and refuge utilizing location and the design criteria in Section 7-01.0.0, Pedestrian Access, of the Technical Standards Manual.

18. Comment: Clearly Show existing or proposed pedestrian circulation along abutting rights-of-way. Such sidewalks must comply with accessibility requirements for the physically disabled and the design criteria in Section 10-01.0.0, Street Technical Standards, of the Technical Standards Manual.

19. Comment: If applicable, Show refuse collection areas, including locations of dumpsters, screening location and materials. For specific information on refuse collection, refer to Section 8-01.0.0, Solid Waste and Recycle Disposal, Collection, and Storage, of the Technical Standards Manual. Refuse collection on all projects shall be designed based on that section, even if collection is to be contracted to a private firm.

20. Comment: If applicable, see Site Landscape review comments as it pertains to the following: show compliance with landscaping and screening requirements by locations, material descriptions, and dimensions. Specific plant or hardscape material shall be detailed on a landscape plan. A detailed landscape plan is required. In accordance with Section 2-11.0.0, Landscape Plan Requirements.

21. Comment: Additional comments may be forthcoming on the next review based on the proposed use.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Corrected CIP development package.
If you have any questions about this transmittal, please contact Ramiro.Olivarez@tucsonaz.gov
Storm to Shade Review REVIEW COMPLETED Comments attached
TW Planning and Engineering Review REVIEW COMPLETED Conditionally Approved; Please maintain 10 foot distance from root-ball nearest to Monitor Well B-0210A. Please refer to Valve map SW311314