Plan Number: CIP-0425-00006
Parcel: 114111150

Review Status: Approved

Review Details: CIP - DEV SITE + COMM STRUCTURE - INITIAL v.1

Plan Number - CIP-0425-00006
Review Name: CIP - DEV SITE + COMM STRUCTURE - INITIAL v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Bldg Permits - Post Review Express REVIEW COMPLETED
Building Official REVIEW COMPLETED
CDRC Post Review Express REVIEW COMPLETED Once plans are between 90-100% external reviewers will be added.
Commercial Building REVIEW COMPLETED Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
1. Please provide the structural calculations; sealed by an Arizona licensed design professional, used to design this project with the next submittal. IBC 107.2.7
2. Please amend the plans to list the required special inspections.
Additionally, provide the City of Tucson Special Inspection Certificate(s) with Parts A and B completed with the next submittal. IBC 107.1 SI form link:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate.pdf

Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
Commercial Electrical REVIEW COMPLETED Initial Commercial Electrical Review

1. Provide complete electrical plans.
2. Provide an Identification Table specifying the equipment and devices called out on the electrical plans in rectangles.
3. Provide Available Fault Current calculations from TEP transformer to all fault paths, 2017 NEC 110.24.
4. Show Panel’s and other equipment with AIC ratings greater to or equal to the Available Fault Currents, 2017 NEC 110.10
Commercial Mechanical REVIEW COMPLETED To qualify as an equipment building, the minimum values of roof solar reflectance and thermal emittance must comply with the provisions of Table C402.3, IECC 2018. Reference: Section C402.1.2, IECC 2018 (see key note 3, sheet 22of 47).
Fire New Construction REVIEW COMPLETED
New Services/JOC REVIEW COMPLETED This is a duplicate item review.
NPPO REVIEW COMPLETED
Outdoor Lighting REVIEW COMPLETED Initial Review CIP-0425-00006 (8317 E SANDSTONE DR TUCSON, AZ 85750)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
2. Full cut-off lighting, installed under canopies, roof overhangs or eaves, are exempt from Lumen Calculation.
3. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1.
4. Show compliance with total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2.
5. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.

6. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

7. Specify any exceptions used.

8. Provide Curfew lighting controls If applicable Per section 403.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
Real Estate REVIEW COMPLETED If any proposed improvements are located outside property lines in public rights-of-way, it will require a Private Improvement Agreement with the Department of Transportation & Mobility or Temporary Revocable Easement with the Real Estate Division (separate processes). If any action is required to address property rights (dedications, easements, etc), please contact the Real Estate Division 520-791-4181.
ROW Engineering Review REVIEW COMPLETED
Site Engineering REVIEW COMPLETED 1. Include the total acreage of disturbance on the plans along with cut/fill quantities.
2. Show on the grading plan the drainage improvement recommendations from the JE Fuller Drainage Assessment Memo.


Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
Site Landscape REVIEW COMPLETED
Site Zoning REVIEW COMPLETED
Traffic Engineering Review REVIEW COMPLETED Traffic Engineering has no comments on this project.
TSMR/PDMR - Engineering REVIEW COMPLETED
TW New Development Review REVIEW COMPLETED CIP-0425-00006 - CIP - Dev Site + Comm Structure - Initial v1 - 8317 E SANDSTONE

The New Development Section has no developer-financed projects in this area that may affect or be affected by this Capital Improvement Project.

No further reviews by Tucson Water’s New Development Section is required.

Tim Rowe, P.E., Civil Engineer
Tucson Water, New Development Section
201 N. Stone Avenue, #2-220
P.O. Box 27210
Tucson, AZ 85726-7210
(520) 837-2106
tim.rowe@tucsonaz.gov
TW Planning and Engineering Review REVIEW COMPLETED No comments, in-house project
PRJ000402 Sandstone Booster D-E
Water - PDSD REVIEW COMPLETED