Plan Number: CIP-0424-00014
Parcel: 10306092J

Review Status: Approved

Review Details: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1

Plan Number - CIP-0424-00014
Review Name: CIP - DEV SITE + COMM STRUCTURE - FINAL v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Site Zoning APPROVED Zoning has no comments based on the submitted plans. A separate demolition permit will be required once the CIP review process is complete and approved. If you have questions about the above comments reach out to Nathan Herrera at Nathan.Herrera@tucsonaz.gov
Building Official REVIEW COMPLETED
CDRC Application Completeness REVIEW COMPLETED TEP external reviewer may be required based on scope of work, see internal note for more details. No other external reviewers required at this time. SB.
CDRC Post Review REVIEW COMPLETED
Commercial Building REVIEW COMPLETED Provide egress lighting plan and demonstrate lighting meets the following. IBC 1008.
1. Provide illumination for the means of egress, including the exit discharge
A. The means of egress illumination level shall not be less than 1 foot-candle at the walking surface.
C. The means of egress illumination shall be supplied by backup power (consisting of storage batteries, unit equipment, or an on-site generator) for a duration of not less than 90 minutes. IBC 1008.3
Commercial Electrical REVIEW COMPLETED See Commercial Building comments pertaining to egress lighting. Revise electrical lighting plan as necessary and resubmit.

Ref: 2018 IBC section 107.2.1, 2017 NEC.
Commercial Mechanical REVIEW COMPLETED
Commercial Plumbing REVIEW COMPLETED
PDSD Application Completeness REVIEW COMPLETED
Site Engineering REVIEW COMPLETED
Traffic Engineering Review REVIEW COMPLETED No comments. Not related to Traffic. This project should not require a Traffic Engineering review.
TW Planning and Engineering Review REVIEW COMPLETED
Water - PDSD REVIEW COMPLETED