Plan Number: CIP-0325-00004
Parcel: 10304001X

Review Status: Requires Resubmit

Review Details: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1

Plan Number - CIP-0325-00004
Review Name: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
Real Estate NOT REQUIRED Please contact the Real Estate Division if any property rights need to be addressed.
Zoning Administration NOT REQUIRED
Archeological Sensitivity - Standard REQUIRES RESUBMIT
Bldg Permits - Post Review Express REVIEW COMPLETED
CDRC Post Review Express REVIEW COMPLETED Please address reviewers' comments for the next review. Once plans are 90-100% we will add any external reviewers for approval. Please fill out the additional info screen to reflect the total site acres and acres of disturbance. Please fill out the Type of review under the additional info screen. If the acres of disturbance are greater than 1 acre, then a dust permit may be required. Thanks
Commercial Building REVIEW COMPLETED 1. Please provide the structural calculations used to design the buildings, shade structures, ramadas and light pole bases, etc.
2. Please amend the structural drawings to provide a statement of special inspections applicable to this project.
3 Please provide detailed construction drawings for buildings, shade structures, ramadas.
Commercial Electrical REVIEW COMPLETED Commercial Electrical Review (60%) CIP-0325-00004 (4300 N SILVERBELL RD TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. Provide a complete electrical plan-set showing all proposed electrical work.
2. Should include but not be limited to:
a) Show the location of the panel on the Electrical Plan with clear working space compliance, 2017 NEC 110.26(A).
b) Provide electrical load calculations, for the Main Service Panel and any Sub-panels, Per NEC 220.40.
c) Provide complete line diagrams for service entrances and sub-panels, to include all transformers and other electrical equipment.
d) Provide a panel schedule showing the circuits that are being modified and added.
e) Designate the circuit number, that corresponds to the panel schedule, at the location of each new or modified light fixture, receptacle, appliance, and equipment disconnect switch, NEC arts;300 and 408.4.
f) Show all wiring methods in detail for all branch circuit wiring along with branch circuit and breaker panel designations and correlate with the panel schedules. NEC arts;300 and 408.4.
g) Grounding and bonding of splashpad equipment and equipotential grid. The fixed metal structures must be electrically Bonded with the perimeter surface and reinforcing steel of the pool as required by ISPSC 302.1 and NEC680.26(B)(7).
h) Show or note that all applicable electrical work shall comply with, Corrosive Environment – NEC 680.14

Contact Jeremy Hamblin with any questions:
Commercial Mechanical REVIEW COMPLETED
Commercial Plumbing REVIEW COMPLETED
Entitlements REVIEW COMPLETED
External Reviewers - Southwest Gas REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
Fire New Construction REVIEW COMPLETED No comments.
New Services/JOC REVIEW COMPLETED Tucson Water – New Area Development has no objection to the proposed work for CIP-0325-00004, provided all existing and proposed irrigation associated with the path improvements is connected to the reclaimed water system surrounding the park. For potable water, tie new services to the 12" CA water main (PN-115-1974) and connect the water meter accordingly.
Outdoor Lighting REVIEW COMPLETED Outdoor Lighting Review (60%) CIP-0325-00004 (4300 N SILVERBELL RD TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).

https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

Outdoor Lighting Review:

1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan
2. Submit catalogue or specification sheets of all proposed new outdoor lighting fixtures illustrating the type of fixture, color temperature, lumens rating and whether full cut-off or unshielded.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
ROW Engineering Review REVIEW COMPLETED Water Work within Silverbell Rd will require Traffic Control and Archeological Monitoring will be required during work.
Separate Right of Way Permit will be required for work within the Right of Way for Water Connection
Site Engineering REVIEW COMPLETED 1. Delineate the 100-year floodplain on the site plans.
2. Proposed work in the floodplain will require a floodplain use permit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
Site Landscape REVIEW COMPLETED PDSD SITE LANDSCAPE/NPPO REVIEW SECTION COMMENTS:

1. Consider including 6 inch depressed landscape areas to receive rainfall only catchment. This can be handled with a simple leader call out on the landscape/planting plan and a general landscape note.

2. In coordination with the above, look to depress all areas receiving new tree plantings.

3. If possible, grade all new/replaced hardscape areas toward the depressed landscape planting areas.

Thank you.
Chad Keller, RLA
chad.keller@tucsonaz.gov
Site Zoning REVIEW COMPLETED CDRC TRANSMITTAL

TO: Development Services Department
Plans Coordination Office

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: Danny Lopez Park
Capital Improvements Project (CIP) - Interim
CIP-0325-00004 (4300 N SILVERBELL RD)

TRANSMITTAL DATE: November 10, 2025
DUE DATE: October 28, 2025

1. COMMENT: 2-06.4.3 - Provide the case number, CIP-0325-00004, adjacent to the title block on each sheet.
2. COMMENT: 2-06.4.7.A.2 – Include a general note with the gross area of the site by square footage and acreage. Include the square footage as well.
3. COMMENT: 2-06.4.7.A.4 – Include a general note stating the "existing and proposed use of the property is Recreation – Parks and Recreation subject to use specific standards 4.9.13.B and C"
4. COMMENT: 2-06.4.7.A.6 – Include a note stating “this project is designed to meet the overlay zone(s) criteria. UDC Article 5.4 Major Streets and Routes Setback Zone (MS&R) – SCENIC CORRIDOR”. Include the statement about Scenic Corridor.
5. COMMENT: 2-06.4.7.A.8.a – Provide the floor area for each building.
6. COMMENT: 2-06.4.7.A.8.b – Provide the percentage of area in square feet of building and accessory building coverage.
7. COMMENT: 2-06.4.7.A.8.c – Provide the percentage of building, lot area, or vehicular use area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included; and,
8. COMMENT: 2-06.4.9.H.5.a – Provide a note stating the required and proposed parking Include the parking ratios.
9. COMMENT: 2-06.4.9.Q – Provide the square footage and height of each proposed building in the footprint of the building.


**For additional information on the any standard presented in this memo, please refer to the City of Tucson “Unified Development Code” – Administrative Manual Section 2-06 or Technical Standards noted in the comments. https://www.tucsonaz.gov/pdsd/all-codes-plans-determinations

If you have any questions about this transmittal, Contact Loran Shamis by email Loran.Shamis@tucsonaz.gov
RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package and comment response letter. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home.
Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf.
Storm to Shade Review REVIEW COMPLETED Comments in Studio Session
TW Planning and Engineering Review REVIEW COMPLETED Please see sheet 7 for comments on placement of walkway and small walls in the vicinity of the 24" reclain water main on the Northeast of the lake
Water - PDSD REVIEW COMPLETED