Review Status: Approved

Review Details: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1

Plan Number - CIP-0325-00003
Review Name: CIP - DEV SITE + COMM STRUCTURE - INTERIM v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
Real Estate NOT REQUIRED
CDRC Post Review Express REVIEW COMPLETED Please address all reviewers' comments for final review.
Commercial Building REVIEW COMPLETED 1. Please provide a statement of special inspections for this project, as well as a list of the required special inspections and tests. IBC 107.2.1, IBC 1704, IBC 1705
Commercial Electrical REVIEW COMPLETED Commercial Electrical Review CIP-0325-00003 (7101 N Casa Grande HWY HY Tucson, AZ 85743)
90% Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

>>> The following comments were not addressed:
1. Provide Fault Current Analysis and show new equipment AIC rating sufficient to withstand the calculated Fault Current. Provide Available Fault Current calculations from TEP transformers to all new equipment, 2017 NEC 110.24.
2. Show new Panel’s and other new equipment with AIC ratings greater than or equal to the Available Fault Currents calculated, 2017 NEC 110.10.
3. Provide electrical load calculations, for the Main Service Panel, Per NEC 220.40.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
External Reviewers - Arizona Department of Transportation (ADOT) REVIEW COMPLETED [EXTERNAL] Re: TDC External Review PERMIT: CIP-0325-00003 Please Sign-In DUE: 8/25/2025
jgomes@azdot.gov
on behalf of
ADOT SC Traffic Engineering - ADOT
​CDRC​
Good Afternoon,

ADOT has no comments on this CIP.

Thank you for the opportunity to review and comment
External Reviewers - Pima Association of Governments REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
External Reviewers - Southwest Gas REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
External Reviewers - Tucson Electric Power (TEP) REVIEW COMPLETED September 23, 2025
WO#T159638
City of Tucson
Planning and Development Services
Attn: CDRC Admin Team
Dear CDRC Admin Team
Subject: Residential Model Plan
CIP-0325-00003
Tucson Electric Power Company (TEP) has reviewed and approved the development
plan submitted 8/11/2025. There are no existing facilities within the development. There
are no apparent conflicts at this time.
Enclosed is a copy of a TEP facilities map showing the approximate location of the
existing facilities. Any relocation costs will be billable to the customer.
To apply for electric service, please call the New Construction department at (520) 918-
8300. Please submit a final set of plans including approved site, electric load, paving
off-site improvements and irrigation plans. If available, include a PDF version of the
plans.
If easements are required, they will be secured by separate instrument. Should you
have any easement questions, please contact our Land Resources Department,
LandReviews@tep.com.
Should you have any technical questions, please contact the area designer,
Roger Asplin
(520) 260-1927
rasplin@tep.com
Sincerely,
Design Admins
Design Admins
Tucson Electric Power
External Reviewers - United States Postal Service (USPS) REVIEW COMPLETED CDRC sent FYI email sent to PAG, USPS, SWG. No further action is required.
Outdoor Lighting REVIEW COMPLETED no comments.
Site Engineering REVIEW COMPLETED Permit: CIP-0325-00003
Location: 7101 N Casa Grande HWY
Review Date: 8/18/2025
Site Engineering Comments:
1. Previous comment was not address, provide cut/fill quantities on the grading/plan set.

If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
Site Zoning REVIEW COMPLETED City of Tucson Zoning does not apply.