Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan: T10FR01695
Plan Details
Apply Date:
08/11/2010
Applicant:
N/A
Description:
FIRE
Completed Inspections
Permit Status:
Permit Number:
Permit Description:
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/11/2010 | INSP - FULL | RDUARTE | Approved | Petition of appeal to the Fire Code Official : TFC 1008.1.8- Egress doors shall be openable from the egress side without use of a keyor special knowledge or effort. EXPLANATION OF WHY CONFORMANCE WITH THE ABOVE REQUIREMENT PRESENTS AN UNUSUAL PROBLEM: Our request is based on the need to enhance and improve our "Infant Abduction Prevention Program" at the Pediatric and Mom-Baby Units (100-200 and 300) that are under construction and expansion at this time. TFD has already granted variance on our existing Pediatric and mom-baby units. STATE SPECIFICALLY WHAT IS PROPOSED IN LIEU OF LITERAL COMPLIANCE. TMC proposes to continue using the badge readers and video phone system to control egress for staff and visitors. During an emergency all doors unlock upon activation of our fire system (fire alarm pull stations, smoke detectors and sprinkler systems). DECISION OF THE FIRE CODE OFFICIAL: APPROVED BY CHIEF DAN UTHE FIRE MARSHAL. |