Plan Details

Status:
Complete
Type:
FIREINSP
Apply Date:
03/01/2010
Applicant:
N/A
Description:
FIRE

Completed Inspections

Permit Status:
Permit Number:
Permit Description:
Total Completed Inspections - 1
Date Description Inspector Results Comments
03/01/2010 INSP - FULL RDUARTE Approved Petition of Appeal to the Fire Code Official for: Transmission channels.

EXPLANATION OF WHY CONFORMATION WITH THE ABOVE REQUIREMENT PRESENTS AN UNUSUAL PROBLEM: Phone service is not available at location. closest Qwest lines are across street. The were not feed under street to building. The only service at building is Cox VOIP based service. These services offer at best 6 hour back up.

STATE SPECIFICALLY WHAT IS PROPOSED IN LIEU OF LITERAL COMPLIANCE: We propose using a listed fire cellular as primary communication and Cox services as backup.

DECISION OF THE FIRE CODE OFFICIAL:
Approved per Chief Dan Uthe Fire Marshal 02/25/10.