Plan: T09FR02510
Plan Details
Apply Date:
07/29/2009
Applicant:
N/A
Description:
FIRE
Completed Inspections
Permit Status:
Permit Number:
Permit Description:
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/29/2009 | INSP - FULL | RDUARTE | Approved | Petition of Appeal to the Fire Code Official- 907.2.3 Manual fire alarm system shall be installed. Explain why conformance of requirement presents unusual problem: System outdated and being upgraded. Favara AFDC will install a fully compliant system as quickly as work can be completed. STATE specifically what is proposed in lieu of literal compliance: A fully compliant system has been authorized and will be installed by Favara. DECISION OF FIRE CODE OFFICIAL: APPROVED WITH STIPULATIONS- A 2-WEEK EXTENSION IS APPROVED WITH THE STIPULATION OF A FIRE WATCH ON DUTY WHILE THE BUILDING IS OCCUPIED. PER CHIEF DAN UTHE. 7/29/2009 |