Permit: TF-FCP-0824-00619
Permit Details
Status:
Complete
Type:
Fire Construction Permit
Address:
7500 E VOYAGER RD UNIT 77
Address NEW:
7500 E VOYAGER RD UNIT 77
Apply Date:
08/02/2024
Applicant:
Chris Cooper
Description:
Install 1000 Gal. U/G Propane Tank and connect to existing Gas Line
Permit Reviews
Permit Number - TF-FCP-0824-00619
Permit Status: Complete
Permit Description: Install 1000 Gal. U/G Propane Tank and connect to existing Gas Line
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 08/05/2024 | FIRE CONSTRUCTION REVIEW v.1 | 08/05/2024 | REQUIRES RESUBMIT |
| 08/14/2024 | FIRE CONSTRUCTION REVIEW v.2 | 09/20/2024 | APPROVED |
Completed Inspections
Permit Status: Complete
Permit Number: TF-FCP-0824-00619
Permit Description: Install 1000 Gal. U/G Propane Tank and connect to existing Gas Line
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2025 | COT - FCON - Tank - Final | Passed | Passed Inspection with note that Inspector was never notified of tank install. Tank was already buried. Met with Zach Trim from Arizona Propane to do CATHODIC PROTECTION (CP) TESTING. This test the integrity of the tank (sufficiently protected from corrosion). reading on meter should be -.8 or greater. The readings were -1.15 and -1.19 (see attached photos) |