Start Date Submittal Complete Date Status  
08/05/2024 FIRE CONSTRUCTION REVIEW v.1 08/05/2024 REQUIRES RESUBMIT Review Details
08/14/2024 FIRE CONSTRUCTION REVIEW v.2 09/20/2024 APPROVED Review Details

Completed Inspections

Permit Status: Complete
Permit Number: TF-FCP-0824-00619
Permit Description: Install 1000 Gal. U/G Propane Tank and connect to existing Gas Line
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/26/2025 COT - FCON - Tank - Final Passed Passed Inspection with note that Inspector was never notified of tank install. Tank was already buried. Met with Zach Trim from Arizona Propane to do CATHODIC PROTECTION (CP) TESTING. This test the integrity of the tank (sufficiently protected from corrosion). reading on meter should be -.8 or greater. The readings were -1.15 and -1.19 (see attached photos)