Permit: TF-FCP-0723-00881
Permit Details
Apply Date:
07/24/2023
Applicant:
Devin Hulsey
Description:
New fire sprinkler system for existing restaurant
Permit Reviews
Permit Number - TF-FCP-0723-00881
Permit Status: Complete
Permit Description: New fire sprinkler system for existing restaurant
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/27/2023 | FIRE CONSTRUCTION REVIEW v.1 | 08/02/2023 | REQUIRES RESUBMIT |
08/07/2023 | FIRE CONSTRUCTION REVIEW v.2 | 08/21/2023 | APPROVED |
Outstanding Inspections
Permit Status: Complete
Permit Number: TF-FCP-0723-00881
Permite Description: New fire sprinkler system for existing restaurant
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/07/2023 | FCON – OH Piping & Hydro | N/A | Partial Pass | 210 psi. Walk in head and the head above the bar need to be relocated, head in the dry storage area needs to be added. |
Completed Inspections
Permit Status: Complete
Permit Number: TF-FCP-0723-00881
Permit Description: New fire sprinkler system for existing restaurant
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/29/2023 | COT - FCON - Sprinkler - Final | Passed | ||
09/29/2023 | FCON – OH Piping & Hydro | Passed |