Description:
PROJECT: HUGHES FEDERAL CREDIT UNION - TENANT IMPROVEMENT LOCATION: TUCSON, ARIZONA SYSTEM TYPE: FIRE ALARM SYSTEM MODIFICATION 1. PROJECT DESCRIPTION THIS PROJECT CONSISTS OF MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM AS PART OF A TENANT IMPROVEMENT FOR HUGHES FEDERAL CREDIT UNION LOCATED IN TUCSON, ARIZONA. WORK INCLUDES RELOCATION, REMOVAL, AND ADDITION OF FIRE ALARM DEVICES IN ACCORDANCE WITH THE ELECTRICAL ENGINEER DRAWINGS. 2. EXISTING SYSTEM THE EXISTING FIRE ALARM CONTROL PANEL, POWER SUPPLIES, INITIATING DEVICES, NOTIFICATION APPLIANCES, CIRCUITS, AND ASSOCIATED EQUIPMENT SHALL REMAIN AND BE REUSED UNLESS OTHERWISE NOTED. ALL DEVICES AND EQUIPMENT NOT SPECIFICALLY IDENTIFIED FOR MODIFICATION SHALL REMAIN AS-IS. 3. NOTIFICATION APPLIANCES RELOCATE, REMOVE, AND INSTALL CEILING-MOUNT NOTIFICATION APPLIANCES AS INDICATED ON THE DRAWINGS. EXISTING POWER SUPPLIES SHALL REMAIN AND BE UTILIZED FOR NEW NOTIFICATION APPLIANCE CIRCUITS. ONE (1) NEW NOTIFICATION APPLIANCE CIRCUIT SHALL BE PROVIDED FROM AN EXISTING POWER SUPPLY. SELECT NEW NOTIFICATION APPLIANCES SHALL BE CONNECTED TO EXISTING NOTIFICATION APPLIANCE CIRCUITS AS INDICATED. ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE INSTALLED AS CLASS A. 4. INITIATING DEVICES RELOCATE AND INSTALL SMOKE DETECTORS AS INDICATED ON THE DRAWINGS. ALL INITIATING DEVICE CIRCUITS SHALL REMAIN CLASS A. 5. WIRING EXISTING WIRING SHALL BE REUSED WHERE FEASIBLE. NEW WIRING SHALL BE INSTALLED AS REQUIRED TO SUPPORT NEW DEVICE LOCATIONS AND CIRCUIT MODIFICATIONS. ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72, APPLICABLE LOCAL CODES, AND MANUFACTURER REQUIREMENTS. ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED AS CLASS A. 6. PROGRAMMING, TESTING, AND ACCEPTANCE MODIFY EXISTING SYSTEM PROGRAMMING AS REQUIRED TO INCORPORATE NEW AND RELOCATED DEVICES. PERFORM FUNCTIONAL TESTING OF ALL MODIFIED, NEWLY INSTALLED, AND RELOCATED DEVICES. VERIFY PROPER OPERATION OF ALL INITIATING DEVICE AND NOTIFICATION APPLIANCE CIRCUITS. COORDINATE FINAL ACCEPTANCE TESTING WITH THE AUTHORITY HAVING JURISDICTION (AHJ). 7. SCOPE LIMITATIONS WORK INCLUDED IN THIS SCOPE IS LIMITED TO THE FIRE ALARM SYSTEM COMPONENTS DESCRIBED HEREIN.
Permit Reviews
Permit Number - TF-FCP-0526-00290
Permit Status: Complete
Permit Description: PROJECT: HUGHES FEDERAL CREDIT UNION - TENANT IMPROVEMENT
LOCATION: TUCSON, ARIZONA
SYSTEM TYPE: FIRE ALARM SYSTEM MODIFICATION
1. PROJECT DESCRIPTION
THIS PROJECT CONSISTS OF MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM AS PART OF A TENANT IMPROVEMENT FOR HUGHES
FEDERAL CREDIT UNION LOCATED IN TUCSON, ARIZONA.
WORK INCLUDES RELOCATION, REMOVAL, AND ADDITION OF FIRE ALARM DEVICES IN ACCORDANCE WITH THE ELECTRICAL ENGINEER
DRAWINGS.
2. EXISTING SYSTEM
THE EXISTING FIRE ALARM CONTROL PANEL, POWER SUPPLIES, INITIATING DEVICES, NOTIFICATION APPLIANCES, CIRCUITS, AND
ASSOCIATED EQUIPMENT SHALL REMAIN AND BE REUSED UNLESS OTHERWISE NOTED.
ALL DEVICES AND EQUIPMENT NOT SPECIFICALLY IDENTIFIED FOR MODIFICATION SHALL REMAIN AS-IS.
3. NOTIFICATION APPLIANCES
RELOCATE, REMOVE, AND INSTALL CEILING-MOUNT NOTIFICATION APPLIANCES AS INDICATED ON THE DRAWINGS.
EXISTING POWER SUPPLIES SHALL REMAIN AND BE UTILIZED FOR NEW NOTIFICATION APPLIANCE CIRCUITS.
ONE (1) NEW NOTIFICATION APPLIANCE CIRCUIT SHALL BE PROVIDED FROM AN EXISTING POWER SUPPLY.
SELECT NEW NOTIFICATION APPLIANCES SHALL BE CONNECTED TO EXISTING NOTIFICATION APPLIANCE CIRCUITS AS INDICATED.
ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE INSTALLED AS CLASS A.
4. INITIATING DEVICES
RELOCATE AND INSTALL SMOKE DETECTORS AS INDICATED ON THE DRAWINGS.
ALL INITIATING DEVICE CIRCUITS SHALL REMAIN CLASS A.
5. WIRING
EXISTING WIRING SHALL BE REUSED WHERE FEASIBLE.
NEW WIRING SHALL BE INSTALLED AS REQUIRED TO SUPPORT NEW DEVICE LOCATIONS AND CIRCUIT MODIFICATIONS.
ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72, APPLICABLE LOCAL CODES, AND MANUFACTURER
REQUIREMENTS.
ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED AS CLASS A.
6. PROGRAMMING, TESTING, AND ACCEPTANCE
MODIFY EXISTING SYSTEM PROGRAMMING AS REQUIRED TO INCORPORATE NEW AND RELOCATED DEVICES.
PERFORM FUNCTIONAL TESTING OF ALL MODIFIED, NEWLY INSTALLED, AND RELOCATED DEVICES.
VERIFY PROPER OPERATION OF ALL INITIATING DEVICE AND NOTIFICATION APPLIANCE CIRCUITS.
COORDINATE FINAL ACCEPTANCE TESTING WITH THE AUTHORITY HAVING JURISDICTION (AHJ).
7. SCOPE LIMITATIONS
WORK INCLUDED IN THIS SCOPE IS LIMITED TO THE FIRE ALARM SYSTEM COMPONENTS DESCRIBED HEREIN.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/12/2026 | FIRE CONSTRUCTION REVIEW v.1 | 06/02/2026 | APPROVED |
Completed Inspections
Permit Status: Complete
Permit Number: TF-FCP-0526-00290
Permit Description: PROJECT: HUGHES FEDERAL CREDIT UNION - TENANT IMPROVEMENT
LOCATION: TUCSON, ARIZONA
SYSTEM TYPE: FIRE ALARM SYSTEM MODIFICATION
1. PROJECT DESCRIPTION
THIS PROJECT CONSISTS OF MODIFICATIONS TO THE EXISTING FIRE ALARM SYSTEM AS PART OF A TENANT IMPROVEMENT FOR HUGHES
FEDERAL CREDIT UNION LOCATED IN TUCSON, ARIZONA.
WORK INCLUDES RELOCATION, REMOVAL, AND ADDITION OF FIRE ALARM DEVICES IN ACCORDANCE WITH THE ELECTRICAL ENGINEER
DRAWINGS.
2. EXISTING SYSTEM
THE EXISTING FIRE ALARM CONTROL PANEL, POWER SUPPLIES, INITIATING DEVICES, NOTIFICATION APPLIANCES, CIRCUITS, AND
ASSOCIATED EQUIPMENT SHALL REMAIN AND BE REUSED UNLESS OTHERWISE NOTED.
ALL DEVICES AND EQUIPMENT NOT SPECIFICALLY IDENTIFIED FOR MODIFICATION SHALL REMAIN AS-IS.
3. NOTIFICATION APPLIANCES
RELOCATE, REMOVE, AND INSTALL CEILING-MOUNT NOTIFICATION APPLIANCES AS INDICATED ON THE DRAWINGS.
EXISTING POWER SUPPLIES SHALL REMAIN AND BE UTILIZED FOR NEW NOTIFICATION APPLIANCE CIRCUITS.
ONE (1) NEW NOTIFICATION APPLIANCE CIRCUIT SHALL BE PROVIDED FROM AN EXISTING POWER SUPPLY.
SELECT NEW NOTIFICATION APPLIANCES SHALL BE CONNECTED TO EXISTING NOTIFICATION APPLIANCE CIRCUITS AS INDICATED.
ALL NOTIFICATION APPLIANCE CIRCUITS SHALL BE INSTALLED AS CLASS A.
4. INITIATING DEVICES
RELOCATE AND INSTALL SMOKE DETECTORS AS INDICATED ON THE DRAWINGS.
ALL INITIATING DEVICE CIRCUITS SHALL REMAIN CLASS A.
5. WIRING
EXISTING WIRING SHALL BE REUSED WHERE FEASIBLE.
NEW WIRING SHALL BE INSTALLED AS REQUIRED TO SUPPORT NEW DEVICE LOCATIONS AND CIRCUIT MODIFICATIONS.
ALL WIRING SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72, APPLICABLE LOCAL CODES, AND MANUFACTURER
REQUIREMENTS.
ALL FIRE ALARM CIRCUITS SHALL BE INSTALLED AS CLASS A.
6. PROGRAMMING, TESTING, AND ACCEPTANCE
MODIFY EXISTING SYSTEM PROGRAMMING AS REQUIRED TO INCORPORATE NEW AND RELOCATED DEVICES.
PERFORM FUNCTIONAL TESTING OF ALL MODIFIED, NEWLY INSTALLED, AND RELOCATED DEVICES.
VERIFY PROPER OPERATION OF ALL INITIATING DEVICE AND NOTIFICATION APPLIANCE CIRCUITS.
COORDINATE FINAL ACCEPTANCE TESTING WITH THE AUTHORITY HAVING JURISDICTION (AHJ).
7. SCOPE LIMITATIONS
WORK INCLUDED IN THIS SCOPE IS LIMITED TO THE FIRE ALARM SYSTEM COMPONENTS DESCRIBED HEREIN.
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2026 | COT - FCON - Alarm - Final | Passed |