Permit: TF-FCP-0326-00189
Permit Details
Status:
Inspections
Type:
Fire Construction Permit
Address:
2929 E CORONA RD
Address NEW:
2929 E CORONA RD
Apply Date:
03/19/2026
Applicant:
Devin Hulsey
Description:
Remove portions of existing systems and install new ESFR systems.
Permit Reviews
Permit Number - TF-FCP-0326-00189
Permit Status: Inspections
Permit Description: Remove portions of existing systems and install new ESFR systems.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/19/2026 | FIRE CONSTRUCTION REVIEW v.1 | 04/10/2026 | APPROVED |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TF-FCP-0326-00189
Permite Description: Remove portions of existing systems and install new ESFR systems.
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2026 | FCON – OH Piping & Hydro | N/A | Partial Pass | OH/Hydro for System 3. Holding pressure at 205psi. Will need to fix or replace leaking Check Valve prior to Sprinkler Final. |