Permit: TF-FCP-0325-00223
Permit Details
Status:
Expired
Type:
Fire Construction Permit
Address:
1020 N WOODLAND AV
Address NEW:
1020 N WOODLAND AV
Apply Date:
03/17/2025
Applicant:
Anthony Dorman
Description:
EXPEDITE Upgrade cellular monitoring
Permit Reviews
Permit Number - TF-FCP-0325-00223
Permit Status: Expired
Permit Description: EXPEDITE
Upgrade cellular monitoring
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/17/2025 | FIRE CONSTRUCTION REVIEW v.1 | 03/18/2025 | APPROVED |
Outstanding Inspections
Permit Status: Expired
Permit Number: TF-FCP-0325-00223
Permite Description: EXPEDITE
Upgrade cellular monitoring
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/03/2025 | COT - FCON - Alarm - Final | N/A | Re-inspection required | A smoke detector needs to be added above the FACP, dialer's back-up batteries need to report the the panel when low or missing, tamper switch supervisory needs to clear when valve is open. |