Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Fire Construction Permit
Address NEW:
6880 E BROADWAY BL
Apply Date:
01/29/2025
Applicant:
Bosch Building Technologies Office
Description:
Install Fire Alarm relay to interface with card access system.

Permit Reviews

Permit Number - TF-FCP-0125-00090
Permit Status: Inspections
Permit Description: Install Fire Alarm relay to interface with card access system.
Start Date Submittal Complete Date Status  
01/30/2025 FIRE CONSTRUCTION REVIEW v.1 02/11/2025 APPROVED Review Details

Outstanding Inspections

Permit Status: Inspections
Permit Number: TF-FCP-0125-00090
Permite Description: Install Fire Alarm relay to interface with card access system.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
COT - FCON - Alarm - Final N/A Not Ready Will need to provide a plan and sequence of operation for Mag Locks installed on Exit Doors. Currently Doors cannot be opened from the inside without an Alarm activation or special Keyed access.

Documents

File Name Document Type  
E85001-0239 -- CONTROL RELAY MODULES_V1.PDF DOCUMENTS VIEW
PLAN SET_V1.PDF DOCUMENTS VIEW