Permit: TC-UTL-0623-00071
Permit Details
Apply Date:
06/15/2023
Applicant:
Brad Farkas
Description:
Installation of new 80' monopole, 30'x30'x8' chain link fence, new telco and electrical service
Permit Reviews
Permit Number - TC-UTL-0623-00071
Permit Status: Issued
Permit Description: Installation of new 80' monopole, 30'x30'x8' chain link fence, new telco and electrical service
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 06/22/2023 | UTILITIES REVIEW v.1 | 07/17/2023 | APPROVED |
| 10/03/2023 | UTILITIES REVIEW v.1 | 11/15/2023 | APPROVED |
| 07/17/2023 | RESTAMP - COMMERCIAL v.1 | 07/20/2023 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-UTL-0623-00071
Permit Status: Issued
Permit Description: Installation of new 80' monopole, 30'x30'x8' chain link fence, new telco and electrical service
Total Outstanding Activity Conditions - 5
| Date | Name |
|---|---|
| 07/17/2023 | Special inspections must be performed by an approved third party inspection agency at the owner's expense. Special inspection forms and reports are required to be submitted for review and approved prior to issuance of final approval documents. |
| 07/17/2023 | The generator shall include a fuel catchment feature designed to contain at least 210 gallons of fuel in the event of a leak. |
| 07/17/2023 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. |
| 07/17/2023 | SPECIAL INSPECTION FOR PILING, DRILLED PIERS AND CAISSONS IS REQUIRED. |
| 07/17/2023 | SPECIAL INSPECTION FOR WELDING IS REQUIRED. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-UTL-0623-00071
Permite Description: Installation of new 80' monopole, 30'x30'x8' chain link fence, new telco and electrical service
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/14/2023 | COT - LCEL - Electrical Underground | N/A | Partial Pass | Partial for the primary conduits from the transformer location to the power pole, okay to backfill progress areas |
| 10/03/2023 | COT - LCEL - Grounding/Bonding | N/A | Partial Pass | Ground bars with Cad-welded connections for ground ring at service panels and tower locations, verbal approval to backfill progress areas was given by TG Partial approval pending plan revision to show ground bars in lieu of ground rods (hard grade) |
| 12/06/2023 | COT - LCBU - Building Final | N/A | Not Applicable | duplicate |
Completed Inspections
Permit Status: Issued
Permit Number: TC-UTL-0623-00071
Permit Description: Installation of new 80' monopole, 30'x30'x8' chain link fence, new telco and electrical service
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2023 | COT - LCEL - Electrical Underground | Passed | Approved underground conduit from service panels to distribution panels, okay to backfill progress areas | |
| 10/06/2023 | COT - LCBU - Excavation/Rebar/Zoning | Passed | ||
| 12/06/2023 | COT - LCEL - Electrical Final | Passed | ||
| 12/06/2023 | BULD - Electrical Clearance | Passed | Approved new service cabinet, ECO Clearance required for meter labeled CS1 |