Permit: TC-SOL-0326-00201
Permit Details
Apply Date:
03/24/2026
Applicant:
Jeff Shoemaker
Description:
3.95kW roof mounted 10 new panels, new 100A AC disconnect
Permit Reviews
Permit Number - TC-SOL-0326-00201
Permit Status: Inspections
Permit Description: 3.95kW roof mounted 10 new panels, new 100A AC disconnect
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/24/2026 | RESIDENTIAL SOLAR APP v.1 | N/A | APPROVED |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-SOL-0326-00201
Permite Description: 3.95kW roof mounted 10 new panels, new 100A AC disconnect
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2026 | COT - RSOL - Electrical Final Solar Project | N/A | Re-inspection required | 08/26/2026 Plans call for 70A backfeed breaker, current field install has 80A. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-SOL-0326-00201
Permit Description: 3.95kW roof mounted 10 new panels, new 100A AC disconnect
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2026 | BULD - Electrical Clearance | Passed | 08/27/2026 Clearance TEP DGC. |
|
| 08/27/2026 | COT - RSOL - Electrical Final Solar Project | Passed | 08/27/2026 Clearance TEP DGC. Verified 70A breaker added. |