Permit: TC-RES-1223-09991
Permit Details
Status:
Issued
Type:
Residential Building - One or Two Family
Address:
5107 E QUARTERMASTER CT
Address NEW:
5107 E QUARTERMASTER CT
Apply Date:
12/08/2023
Applicant:
Katharine Kent
Description:
Upgrading MSP from 300A to 400A service panel.
Permit Reviews
Permit Number - TC-RES-1223-09991
Permit Status: Issued
Permit Description: Upgrading MSP from 300A to 400A service panel.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/08/2023 | RESIDENTIAL SIMPLE REVIEW v.1 | 12/08/2023 | REQUIRES RESUBMIT |
| 12/13/2023 | RESIDENTIAL SIMPLE REVIEW v.2 | 12/14/2023 | APPROVED |
Completed Inspections
Permit Status: Issued
Permit Number: TC-RES-1223-09991
Permit Description: Upgrading MSP from 300A to 400A service panel.
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2024 | COT - RSEL - Electrical Final | Passed | Electricians have removed old service panel and installed new electrical service panel and meter box. Bonds have been installed on gas and water lines, 2-new grounding rods have been driven into the ground 6' apart. Panel cover has new address plate installed. Wires are being landed to ground bus, neutral bus, and the correct sized breaker. | |
| 02/07/2024 | RSEL - Electrical Progress | Passed | Electricians have removed old service panel and installed new electrical service panel and meter box. Panel cover has new address plate installed. Wires are being landed to ground bus, neutral bus, and the correct sized breaker. | |
| 02/07/2024 | BULD - Electrical Clearance | Passed | Electricians have removed old service panel and installed new electrical service panel and meter box. Bonds have been installed on gas and water lines, 2-new grounding rods have been driven into the ground 6' apart. Panel cover has new address plate installed. Wires are being landed to ground bus, neutral bus, and the correct sized breaker. | |
| 02/07/2024 | COT - RSEL - Electrical Underground | Passed | Not Applicable: Electrical wiring from transformer to panel is existing. |