Permit: TC-RES-1025-04911
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
7521 E FAIRMOUNT PL
Address NEW:
7521 E FAIRMOUNT PL
Apply Date:
10/08/2025
Applicant:
christopher Dilts
Description:
currently 200 amp Millbank meter feeds 100 amp fpe split bus. Fpe is feeding 200 amp main breaker panel via 100 amp breaker. Plan is to power kill. remove old FPE split bus and replance with 12 x 12 x 8 juncetion box. feed 200 amp main breaker panel from existing meter socket via 2" and 4/0 three wire. 1 1/2" conduit from 200 amp panel to junction box re-feed 100 amp sub panel with #4 al.
Permit Reviews
Permit Number - TC-RES-1025-04911
Permit Status: Complete
Permit Description: currently 200 amp Millbank meter feeds 100 amp fpe split bus. Fpe is feeding 200 amp main breaker panel via 100 amp breaker. Plan is to power kill. remove old FPE split bus and replance with 12 x 12 x 8 juncetion box. feed 200 amp main breaker panel from existing meter socket via 2" and 4/0 three wire. 1 1/2" conduit from 200 amp panel to junction box re-feed 100 amp sub panel with #4 al.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/08/2025 | RESIDENTIAL SIMPLE REVIEW v.1 | 10/08/2025 | APPROVED |
Conditions
Permit Number - TC-RES-1025-04911
Permit Status: Complete
Permit Description: currently 200 amp Millbank meter feeds 100 amp fpe split bus. Fpe is feeding 200 amp main breaker panel via 100 amp breaker. Plan is to power kill. remove old FPE split bus and replance with 12 x 12 x 8 juncetion box. feed 200 amp main breaker panel from existing meter socket via 2" and 4/0 three wire. 1 1/2" conduit from 200 amp panel to junction box re-feed 100 amp sub panel with #4 al.
| Date | Description | Comments |
|---|---|---|
| 10/08/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-RES-1025-04911
Permite Description: currently 200 amp Millbank meter feeds 100 amp fpe split bus. Fpe is feeding 200 amp main breaker panel via 100 amp breaker. Plan is to power kill. remove old FPE split bus and replance with 12 x 12 x 8 juncetion box. feed 200 amp main breaker panel from existing meter socket via 2" and 4/0 three wire. 1 1/2" conduit from 200 amp panel to junction box re-feed 100 amp sub panel with #4 al.
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2026 | RSEL - Electrical Progress | N/A | Not Applicable | |
| 03/26/2026 | COT - RSEL - Electrical Underground | N/A | Not Applicable |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-1025-04911
Permit Description: currently 200 amp Millbank meter feeds 100 amp fpe split bus. Fpe is feeding 200 amp main breaker panel via 100 amp breaker. Plan is to power kill. remove old FPE split bus and replance with 12 x 12 x 8 juncetion box. feed 200 amp main breaker panel from existing meter socket via 2" and 4/0 three wire. 1 1/2" conduit from 200 amp panel to junction box re-feed 100 amp sub panel with #4 al.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2025 | BULD - Electrical Clearance | Passed | Verbal clearance to TEP INCR. 10/21/2025 | |
| 10/21/2025 | COT - RSEL - Electrical Final | Passed |