Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
2503 E MENOR SV
Address NEW:
2503 E MENOR SV
Apply Date:
09/12/2024
Applicant:
Jeff Heisler
Description:
(1) 3.5 ton condenser in back yard changeout like for like (1) 3.5 indoor coil changeout (1) 80K BTUS furnace in closet changeout like for like

Permit Reviews

Permit Number - TC-RES-0924-05314
Permit Status: Inspections
Permit Description: (1) 3.5 ton condenser in back yard changeout like for like (1) 3.5 indoor coil changeout (1) 80K BTUS furnace in closet changeout like for like
Start Date Submittal Complete Date Status  
09/13/2024 RESIDENTIAL SIMPLE REVIEW v.1 09/16/2024 APPROVED Review Details

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-RES-0924-05314
Permite Description: (1) 3.5 ton condenser in back yard changeout like for like (1) 3.5 indoor coil changeout (1) 80K BTUS furnace in closet changeout like for like
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
10/07/2024 RSME - Mechanical Progress N/A Re-inspection required 10/7/24: refrigerant lines must be insulated and UV protected, tape must be removed at double wall pipe at b-vent. condensate pump shall not be wired into furnace.
10/07/2024 COT - RSME - Mechanical Final N/A Re-inspection required 10/7/24: refrigerant lines must be insulated and UV protected, tape must be removed at double wall pipe at b-vent. condensate pump shall not be wired into furnace.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
SITE MAP_V1.PDF DOCUMENTS VIEW