Permit: TC-RES-0525-02571
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
8332 E BEVERLY ST
Address NEW:
8332 E BEVERLY ST
Apply Date:
05/14/2025
Applicant:
Parker and Sons Environmental Conditioning LLC
Description:
Emergency Permit upgrade 100A to 200A Main Service Panel (All in One)
Permit Reviews
Permit Number - TC-RES-0525-02571
Permit Status: Complete
Permit Description: Emergency Permit upgrade 100A to 200A Main Service Panel (All in One)
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/14/2025 | RESIDENTIAL SIMPLE REVIEW v.1 | 05/14/2025 | APPROVED |
Conditions
Permit Number - TC-RES-0525-02571
Permit Status: Complete
Permit Description: Emergency Permit upgrade 100A to 200A Main Service Panel (All in One)
| Date | Description | Comments |
|---|---|---|
| 05/14/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0525-02571
Permit Description: Emergency Permit upgrade 100A to 200A Main Service Panel (All in One)
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2025 | BULD - Electrical Clearance | Passed | 5-23-25 INCR - TEP ready for verbal clearance. Accurate schedule at panel present, riser secured and sealed with flashing, braces in place, lugs torqued to spec (75lb as reported), neutral marked in box and above roof, bonded and grounded, rods 6ft apart. | |
| 05/23/2025 | COT - RSEL - Electrical Final | Passed | 5-23-25 INCR - TEP ready for verbal clearance. Accurate schedule at panel present, riser secured and sealed with flashing, braces in place, lugs torqued to spec (75lb as reported), neutral marked in box and above roof, bonded and grounded, rods 6ft apart. |