Permit: TC-RES-0425-02190
Permit Details
Status:
Complete
Type:
Residential Building - One or Two Family
Address:
1700 S CEYLON PL
Address NEW:
1700 S CEYLON PL
Apply Date:
04/24/2025
Applicant:
John Gruber
Description:
Rheem 40 gallon gas water heater, ser#M082512179, model#XG40T06EC36U1, 36,000BTU. Location closet with high low vents, drip pan w/cap, vent hood secured, T&P to drip pan 4” above pan, sediment trap on gas control valve, new flex lines, new ball valve. Water heater vent hood was not secure, used self tapping screws to secure vent hood up to double wall vent in ceiling, removed vent tape. Also T&P drain the was installed into base of the drip pan, cut drain higher so it is 4” above the drip pan.
Permit Reviews
Permit Number - TC-RES-0425-02190
Permit Status: Complete
Permit Description: Rheem 40 gallon gas water heater, ser#M082512179, model#XG40T06EC36U1, 36,000BTU. Location closet with high low vents, drip pan w/cap, vent hood secured, T&P to drip pan 4” above pan, sediment trap on gas control valve, new flex lines, new ball valve.
Water heater vent hood was not secure, used self tapping screws to secure vent hood up to double wall vent in ceiling, removed vent tape. Also T&P drain the was installed into base of the drip pan, cut drain higher so it is 4” above the drip pan.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/25/2025 | RESIDENTIAL SIMPLE REVIEW v.1 | 04/25/2025 | APPROVED |
Conditions
Permit Number - TC-RES-0425-02190
Permit Status: Complete
Permit Description: Rheem 40 gallon gas water heater, ser#M082512179, model#XG40T06EC36U1, 36,000BTU. Location closet with high low vents, drip pan w/cap, vent hood secured, T&P to drip pan 4” above pan, sediment trap on gas control valve, new flex lines, new ball valve.
Water heater vent hood was not secure, used self tapping screws to secure vent hood up to double wall vent in ceiling, removed vent tape. Also T&P drain the was installed into base of the drip pan, cut drain higher so it is 4” above the drip pan.
| Date | Description | Comments |
|---|---|---|
| 04/25/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0425-02190
Permit Description: Rheem 40 gallon gas water heater, ser#M082512179, model#XG40T06EC36U1, 36,000BTU. Location closet with high low vents, drip pan w/cap, vent hood secured, T&P to drip pan 4” above pan, sediment trap on gas control valve, new flex lines, new ball valve.
Water heater vent hood was not secure, used self tapping screws to secure vent hood up to double wall vent in ceiling, removed vent tape. Also T&P drain the was installed into base of the drip pan, cut drain higher so it is 4” above the drip pan.
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2025 | COT - RSME - Mechanical Final | Passed | Passed 5/2/25 | |
| 05/07/2025 | COT - RSPL - Plumbing Final | Passed | Approved WH installation |