Permit Details

Status:
Complete
Type:
Residential Building - One or Two Family
Address:
2236 E 8TH ST
Address NEW:
2236 E 8TH ST
Apply Date:
04/07/2025
Applicant:
Hailey McGraw
Description:
install 13.12kw residential roof mounted solar and 175A derated main breaker

Permit Reviews

Permit Number - TC-RES-0425-01806
Permit Status: Complete
Permit Description: install 13.12kw residential roof mounted solar and 175A derated main breaker
Start Date Submittal Complete Date Status  
04/09/2025 RESIDENTIAL SOLAR v.1 06/03/2025 APPROVED Review Details

Completed Inspections

Permit Status: Complete
Permit Number: TC-RES-0425-01806
Permit Description: install 13.12kw residential roof mounted solar and 175A derated main breaker
Total Completed Inspections - 4
Date Description Inspector Results Comments
06/27/2025 BULD - Electrical Clearance Passed 6.27.25
PV system is installed per plans. Proper sized conductors used throughout and verified. Proper labels and markings verified on conduits and panels. Panel schedule verified. Grounding and bonding verified. White at neutrals. All panels and PV panels properly secured.
06/27/2025 COT - RSOL - Grounding/Bonding Solar Project Passed 6.27.25
PV system is installed per plans. Proper sized conductors used throughout and verified. Proper labels and markings verified on conduits and panels. Panel schedule verified. Grounding and bonding verified. White at neutrals. All panels and PV panels properly secured.
06/27/2025 RSBU - Building Final Passed 6.27.25
PV system is installed per plans. Proper sized conductors used throughout and verified. Proper labels and markings verified on conduits and panels. Panel schedule verified. Grounding and bonding verified. White at neutrals. All panels and PV panels properly secured.
06/27/2025 COT - RSOL - Electrical Final Solar Project Passed 6.27.25
PV system is installed per plans. Proper sized conductors used throughout and verified. Proper labels and markings verified on conduits and panels. Panel schedule verified. Grounding and bonding verified. White at neutrals. All panels and PV panels properly secured.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-PV PLANS_V1.PDF DOCUMENTS VIEW
STRUC_V1.PDF DOCUMENTS VIEW