Description:
Cut out bad section of black iron near meter and replaced with new mega press and black iron fittings. Pressure test entire gas system and found two other leaks inside home. One leak is at a 3/4-in black iron 90 feeding the cooktop the second leak was at the cooktop shut off valve. Replace both leaking fittings Pressure test entire system up to 15 psi.
Permit Reviews
Permit Number - TC-RES-0226-01034
Permit Status: Complete
Permit Description: Cut out bad section of black iron near meter and replaced with new mega press and black iron fittings.
Pressure test entire gas system and found two other leaks inside home.
One leak is at a 3/4-in black iron 90 feeding the cooktop the second leak was at the cooktop shut off valve.
Replace both leaking fittings
Pressure test entire system up to 15 psi.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/27/2026 | RESIDENTIAL SIMPLE REVIEW v.1 | 03/02/2026 | APPROVED |
Conditions
Permit Number - TC-RES-0226-01034
Permit Status: Complete
Permit Description: Cut out bad section of black iron near meter and replaced with new mega press and black iron fittings.
Pressure test entire gas system and found two other leaks inside home.
One leak is at a 3/4-in black iron 90 feeding the cooktop the second leak was at the cooktop shut off valve.
Replace both leaking fittings
Pressure test entire system up to 15 psi.
| Date | Description | Comments |
|---|---|---|
| 02/27/2026 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit is required prior to issuance of permit. The Affidavit form is available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-RES-0226-01034
Permite Description: Cut out bad section of black iron near meter and replaced with new mega press and black iron fittings.
Pressure test entire gas system and found two other leaks inside home.
One leak is at a 3/4-in black iron 90 feeding the cooktop the second leak was at the cooktop shut off valve.
Replace both leaking fittings
Pressure test entire system up to 15 psi.
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2026 | RSBU - Building Final | N/A | Not Ready | |
| 03/05/2026 | COT - RSPL - Plumbing Final | N/A | Not Ready | |
| 03/05/2026 | COT - BULD - SWG Clearance | N/A | Not Ready |
Completed Inspections
Permit Status: Complete
Permit Number: TC-RES-0226-01034
Permit Description: Cut out bad section of black iron near meter and replaced with new mega press and black iron fittings.
Pressure test entire gas system and found two other leaks inside home.
One leak is at a 3/4-in black iron 90 feeding the cooktop the second leak was at the cooktop shut off valve.
Replace both leaking fittings
Pressure test entire system up to 15 psi.
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2026 | RSBU - Building Final | Passed | 3.9.26 Approved System installed per plans |
|
| 03/09/2026 | COT - RSPL - Plumbing Final | Passed | 3.9.26 Approved System installed per plans |
|
| 03/09/2026 | COT - BULD - SWG Clearance | Passed | 3.9.26 Approved for SWG clearance Pressure verified |