Permit: TC-RES-0225-01037
Permit Details
Status:
Inspections
Type:
Residential Building - One or Two Family
Address:
12718 E LAUREN CANYON PL
Address NEW:
12718 E LAUREN CANYON PL
Apply Date:
02/25/2025
Applicant:
Jayson Myers
Description:
Spa electric run with 50 amp shut off
Permit Reviews
Permit Number - TC-RES-0225-01037
Permit Status: Inspections
Permit Description: Spa electric run with 50 amp shut off
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/25/2025 | RESIDENTIAL SIMPLE REVIEW v.1 | 02/27/2025 | APPROVED |
Conditions
Permit Number - TC-RES-0225-01037
Permit Status: Inspections
Permit Description: Spa electric run with 50 amp shut off
| Date | Description | Comments |
|---|---|---|
| 02/25/2025 | Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit. |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-RES-0225-01037
Permite Description: Spa electric run with 50 amp shut off
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/30/2025 | COT - LCEL - Grounding/Bonding | N/A | Re-inspection required | 4/30/25: no access to home, 1" conduit at main panel must be schedule 80 above ground, 1" conduit must be properly secured, 1" conduit threaded coupling has no glue, threaded fitting must be properly secured at main panel. |
Completed Inspections
Permit Status: Inspections
Permit Number: TC-RES-0225-01037
Permit Description: Spa electric run with 50 amp shut off
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2025 | COT - RSEL - Electrical Underground | Passed | 4 April 25 Ok to backfill. |
|
| 05/12/2025 | COT - RSEL - Electrical Final | Passed | 5/12/25 Pass |
|
| 05/12/2025 | BULD - Electrical Clearance | Passed | 5/12/25 Pass |