Start Date Submittal Complete Date Status  
02/25/2025 RESIDENTIAL SIMPLE REVIEW v.1 02/27/2025 APPROVED Review Details

Conditions

Permit Number - TC-RES-0225-01037
Permit Status: Inspections
Permit Description: Spa electric run with 50 amp shut off
Date Description Comments
02/25/2025 Contractor with active Arizona Contractor's License for specified scope of work, or a signed Owner Builder Affidavit https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/pdsd_owner_builder_affidavit_081623.pdf, is required prior to issuance of permit. Contractor or Owner must have a TDC Online account and be added to the permit as the correct contact type https://www.tucsonaz.gov/files/sharedassets/public/v/2/pdsd/documents/tdc-faq/new-pdfs/adding-additional-contacts.pdf. If you are providing an Owner Builder Affidavit, the owner MUST be attached as a contact on the permit.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-RES-0225-01037
Permite Description: Spa electric run with 50 amp shut off
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
04/30/2025 COT - LCEL - Grounding/Bonding N/A Re-inspection required 4/30/25: no access to home, 1" conduit at main panel must be schedule 80 above ground, 1" conduit must be properly secured, 1" conduit threaded coupling has no glue, threaded fitting must be properly secured at main panel.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-RES-0225-01037
Permit Description: Spa electric run with 50 amp shut off
Total Completed Inspections - 3
Date Description Inspector Results Comments
04/04/2025 COT - RSEL - Electrical Underground Passed 4 April 25
Ok to backfill.
05/12/2025 COT - RSEL - Electrical Final Passed 5/12/25
Pass
05/12/2025 BULD - Electrical Clearance Passed 5/12/25
Pass