Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Complete
Type:
Commercial Building
Address NEW:
1655 W AJO WY UNIT 379
Apply Date:
12/31/2025
Applicant:
David Felix
Description:
Main line replace only

Permit Reviews

Permit Number - TC-COM-1225-02351
Permit Status: Complete
Permit Description: Main line replace only
Start Date Submittal Complete Date Status  
12/31/2025 COMMERCIAL PDSD SIMPLE REVIEW v.1 01/06/2026 APPROVED Review Details
01/13/2026 ADMINISTRATIVE v.2 01/13/2026 APPROVED Review Details
01/06/2026 ADMINISTRATIVE v.1 01/06/2026 REQUIRES RESUBMIT Review Details

Conditions

Permit Number - TC-COM-1225-02351
Permit Status: Complete
Permit Description: Main line replace only
Date Description Comments
12/31/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Completed Inspections

Permit Status: Complete
Permit Number: TC-COM-1225-02351
Permit Description: Main line replace only
Total Completed Inspections - 3
Date Description Inspector Results Comments
01/28/2026 COT - BULD - SWG Clearance Passed 1-28-26: okay to energize meter TG& E172623. Clearance issued to SWG.
01/28/2026 COT - LCPL - Gas Pressure Test Passed 1-28-26: gas pressure test verified at 15psi.
01/28/2026 COT - LCPL - Plumbing Final Passed 1-28-26: verified trench depth at 18" for a new 10' gas yard line. Tracer wire in place, shut off valve and 10 mil tape at riser. Okay to backfill progress areas.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
EPSON_12292025084418_V1.PDF DOCUMENTS VIEW