Permit Details

Status:
Inspections
Type:
Commercial Building
Address NEW:
7170 E BROADWAY BL
Apply Date:
12/12/2024
Applicant:
David Smith
Description:
REPLACE THREE ROOFTOP PACKAGE HVAC UNITS WITH LIKE FOR LIKE EQUIPMENT. NO MODIFICATIONS REQUIRED.

Permit Reviews

Permit Number - TC-COM-1224-02342
Permit Status: Inspections
Permit Description: REPLACE THREE ROOFTOP PACKAGE HVAC UNITS WITH LIKE FOR LIKE EQUIPMENT. NO MODIFICATIONS REQUIRED.
Start Date Submittal Complete Date Status  
12/13/2024 COMMERCIAL PDSD SIMPLE REVIEW v.1 12/14/2024 REQUIRES RESUBMIT Review Details
06/18/2025 COMMERCIAL PDSD SIMPLE REVIEW v.2 06/18/2025 APPROVED Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-1224-02342
Permit Status: Inspections
Permit Description: REPLACE THREE ROOFTOP PACKAGE HVAC UNITS WITH LIKE FOR LIKE EQUIPMENT. NO MODIFICATIONS REQUIRED.
Total Outstanding Activity Conditions - 1
Date Name
06/18/2025 AIR BALANCING REPORT SHOWING THE TOTAL AIRFLOW AND THE OUTSIDE AIRFLOW OF EACH HEAT PUMP IS REQUIRED.

Conditions

Permit Number - TC-COM-1224-02342
Permit Status: Inspections
Permit Description: REPLACE THREE ROOFTOP PACKAGE HVAC UNITS WITH LIKE FOR LIKE EQUIPMENT. NO MODIFICATIONS REQUIRED.
Date Description Comments
12/13/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-1224-02342
Permite Description: REPLACE THREE ROOFTOP PACKAGE HVAC UNITS WITH LIKE FOR LIKE EQUIPMENT. NO MODIFICATIONS REQUIRED.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
08/04/2025 COT - LCME - Mechanical Intermediate N/A Re-inspection required 8/4/25
1. Units are missing coil guards.
2. Units are missing appropriate electrical identification.Please label each unit on the rooftop with circuit number and the panel board that supplies power to unit.Also, label the circuit breakers in panels accordingly.
3. Customer does not have access to Thermostat.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-COM-1224-02342
Permit Description: REPLACE THREE ROOFTOP PACKAGE HVAC UNITS WITH LIKE FOR LIKE EQUIPMENT. NO MODIFICATIONS REQUIRED.
Total Completed Inspections - 1
Date Description Inspector Results Comments
07/30/2025 COT - LCME - Mechanical Final Passed

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-HOME GOODS TUCSON AZ - MECH - 061325_V2.PDF DOCUMENTS VIEW
HOME GOODS TUCSON AZ - ENER - 061325_V2.PDF DOCUMENTS VIEW