Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Inspections
Type:
Commercial Building
Address NEW:
3686 E 3RD ST UNIT 4B
Apply Date:
12/10/2024
Applicant:
Clinton Long
Description:
Reconnect electrical line to meter located on the Southeast side of the building next to unit 4A. This is a single meter.

Permit Reviews

Permit Number - TC-COM-1224-02329
Permit Status: Inspections
Permit Description: Reconnect electrical line to meter located on the Southeast side of the building next to unit 4A. This is a single meter.
Start Date Submittal Complete Date Status  
12/11/2024 COMMERCIAL PDSD SIMPLE REVIEW v.1 12/11/2024 APPROVED Review Details

Conditions

Permit Number - TC-COM-1224-02329
Permit Status: Inspections
Permit Description: Reconnect electrical line to meter located on the Southeast side of the building next to unit 4A. This is a single meter.
Date Description Comments
12/11/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-1224-02329
Permite Description: Reconnect electrical line to meter located on the Southeast side of the building next to unit 4A. This is a single meter.
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
12/13/2024 COT - LCEL - Electrical Final N/A Partial Pass 12-13-24,Unit's 4A, 4B, 5,6, and 7 are powered by a 4pack main panel. I provided TEP with a verbal clearance for reconnect. However, we will have to return for final once the following items have been corrected. Unit 4A-reconnect bathroom fan, unit 4B-missing light fixture globes, unit 5-missing globes, unit 6-nothing noted, and unit 7-missing living room fixture.
12/13/2024 BULD - Electrical Clearance N/A Partial Pass 12-13-24,Unit's 4A, 4B, 5,6, and 7 are powered by a 4pack main panel. I provided TEP with a verbal clearance for reconnect. However, we will have to return for final once the following items have been corrected. Unit 4A-reconnect bathroom fan, unit 4B-missing light fixture globes, unit 5-missing globes, unit 6-nothing noted, and unit 7-missing living room fixture.

Documents

File Name Document Type  
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
3686 E 3RD ST COMMERCIAL TRADE PERMIT MA (1)_V1.PDF DOCUMENTS VIEW