Type:
Commercial Building
Address NEW:
3686 E 3RD ST UNIT 4A
Apply Date:
12/10/2024
Applicant:
Clinton Long
Description:
Reconnect repaired electrical lines to meters located on the southeast corner of the building by 4A. The 4 pack provides electricity to units 4A, 5, 6 and 7.

Permit Reviews

Permit Number - TC-COM-1224-02328
Permit Status: Inspections
Permit Description: Reconnect repaired electrical lines to meters located on the southeast corner of the building by 4A. The 4 pack provides electricity to units 4A, 5, 6 and 7.
Start Date Submittal Complete Date Status  
12/11/2024 COMMERCIAL PDSD SIMPLE REVIEW v.1 12/11/2024 APPROVED Review Details

Conditions

Permit Number - TC-COM-1224-02328
Permit Status: Inspections
Permit Description: Reconnect repaired electrical lines to meters located on the southeast corner of the building by 4A. The 4 pack provides electricity to units 4A, 5, 6 and 7.
Date Description Comments
12/11/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.

Outstanding Inspections

Permit Status: Inspections
Permit Number: TC-COM-1224-02328
Permite Description: Reconnect repaired electrical lines to meters located on the southeast corner of the building by 4A. The 4 pack provides electricity to units 4A, 5, 6 and 7.
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
12/13/2024 COT - LCEL - Electrical Final N/A Partial Pass 12-13-24,Unit's 4A, 4B, 5,6, and 7 are powered by a 4pack main panel. I provided TEP with a verbal clearance for reconnect. However, we will have to return for final once the following items have been corrected. Unit 4A-reconnect bathroom fan, unit 4B-missing light fixture globes, unit 5-missing globes, unit 6-nothing noted, and unit 7-missing living room fixture.

Completed Inspections

Permit Status: Inspections
Permit Number: TC-COM-1224-02328
Permit Description: Reconnect repaired electrical lines to meters located on the southeast corner of the building by 4A. The 4 pack provides electricity to units 4A, 5, 6 and 7.
Total Completed Inspections - 1
Date Description Inspector Results Comments
12/13/2024 BULD - Electrical Clearance Passed 12-13-24,Unit's 4A, 4B, 5,6, and 7 are powered by a 4pack main panel. I provided TEP with a verbal clearance for reconnect. However, we will have to return for final once the following items have been corrected. Unit 4A-reconnect bathroom fan, unit 4B-missing light fixture globes, unit 5-missing globes, unit 6-nothing noted, and unit 7-missing living room fixture.