Permit: TC-COM-1125-02133
Permit Details
Status:
Complete
Type:
Commercial Building
Address:
2900 E BROADWAY BL UNIT 113
Address NEW:
2900 E BROADWAY BL UNIT 113
Apply Date:
11/20/2025
Applicant:
Josh Muckenthaler
Description:
Tenant Improvement of Space for Golf Simulator
Permit Reviews
Permit Number - TC-COM-1125-02133
Permit Status: Complete
Permit Description: Tenant Improvement of Space for Golf Simulator
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/31/2025 | RESTAMP - COMMERCIAL v.1 | 01/21/2026 | APPROVED |
| 12/31/2025 | COMMERCIAL REVIEW - FULL v.2 | 12/31/2025 | APPROVED |
| 11/26/2025 | COMMERCIAL REVIEW - FULL v.1 | 12/23/2025 | REQUIRES RESUBMIT |
| 04/09/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 04/13/2026 | APPROVED |
Conditions
Permit Number - TC-COM-1125-02133
Permit Status: Complete
Permit Description: Tenant Improvement of Space for Golf Simulator
| Date | Description | Comments |
|---|---|---|
| 12/17/2025 | AIR BALANCING REPORT IS REQUIRED. | |
| 12/12/2025 | SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED. | |
| 12/12/2025 | SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED. | |
| 11/26/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 12/12/2025 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
| 12/12/2025 | SPECIAL INSPECTION FOR FOUNDATION/EXCAVATION IS REQUIRED. | |
| 12/12/2025 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. | |
| 12/12/2025 | SPECIAL INSPECTION FOR INSULATING CONCRETE FILL IS REQUIRED. | |
| 12/12/2025 | ??? Designs must be submitted and approved prior to ... | |
| 11/26/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. | |
| 12/17/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-COM-1125-02133
Permite Description: Tenant Improvement of Space for Golf Simulator
Total Outstanding Inspections - 14
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2026 | COT - HCBU - Exterior Clips/Sheathing | N/A | Not Applicable | |
| 03/31/2026 | COT - HCBU - Firewall/Fire Barrier/Firestop | N/A | Not Applicable | |
| 03/31/2026 | COT - FCON - Fire - Final | N/A | Partial Pass | Keyed deadbolt locks shall be a thumb turn on exit doors, sign above exit doors shall be added "This door shall remain unlocked while building is occupied". A sign shall be added to the exterior two rear doors that are no longer in use "This Door Blocked". Fire extinguishers shall be mounted to the wall, emergency light shall be added to the poker room. |
| 04/03/2026 | COT - HCBU - TCO | N/A | Not Applicable | |
| 04/03/2026 | COT - HCBU - Interior Shear Bracing | N/A | Not Applicable | |
| 04/03/2026 | COT - HCBU - Roof Nailing | N/A | Not Applicable | |
| 04/03/2026 | COT - HCBU - Excavation/Rebar/Zoning | N/A | Not Applicable | |
| 04/03/2026 | BULD - Electrical Clearance | N/A | Not Applicable | |
| 04/03/2026 | COT - BULD - SWG Clearance | N/A | Not Applicable | |
| 04/03/2026 | COT - HCBU - Stem Wall/Retaining Wall | N/A | Not Applicable | |
| 04/03/2026 | COT - HCEL - Electrical Progress | N/A | Not Applicable | |
| 04/03/2026 | COT - HCME - Mechanical Progress | N/A | Not Applicable | |
| 04/03/2026 | COT - HCME - Venting | N/A | Not Applicable | |
| 04/03/2026 | PDSD Heavy Commercial Building Division Pre-Construction Meeting | N/A | Not Applicable |
Completed Inspections
Permit Status: Complete
Permit Number: TC-COM-1125-02133
Permit Description: Tenant Improvement of Space for Golf Simulator
Total Completed Inspections - 23