Permit Details

Status:
Needs Resubmittal
Type:
Commercial Building
Address NEW:
4502 S CAMPBELL AV
Apply Date:
10/14/2026
Applicant:
Jelaire Fluit
Description:
Fuel canopy associated with permit TC-COM-0826-01409

Permit Reviews

Permit Number - TC-COM-1026-01694
Permit Status: Needs resubmittal
Permit Description: Fuel canopy associated with permit TC-COM-0826-01409
Start Date Submittal Complete Date Status  
10/20/2026 COMMERCIAL REVIEW - FULL v.1 11/12/2026 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-1026-01694
Permit Status: Needs resubmittal
Permit Description: Fuel canopy associated with permit TC-COM-0826-01409
Total Outstanding Activity Conditions - 12
Date Name
10/20/2026 Pre-Issuance - Required Documents - Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
10/20/2026 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
11/09/2026 Prior to Final - Special Inspections - SPECIAL INSPECTION FOR BOLTS INSTALLED IN CONCRETE IS REQUIRED.
11/09/2026 Prior to Final - Special Inspections - SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
11/09/2026 Obtain ADEQ approval and submit the document prior to issuance of permit. (The state purpose is to protect public health and the environment from releases (i.e., spills, leaks, emissions, etc.) of petroleum and other regulated hazardous substances into groundwater, surface water or soils)
11/09/2026 Prior to Final - Special Inspections - SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED.
11/09/2026 Prior to Final - Required Documents - Post-Installed Anchor Inspection Report is required.
11/09/2026 Prior to Final - Special Inspections - SPECIAL INSPECTION FOR REINFORCING STEEL IS REQUIRED.
11/09/2026 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.
11/09/2026 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
11/09/2026 SPECIAL INSPECTION FOR STRUCTURAL STEEL FRAMES IS REQUIRED.
11/09/2026 SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED.