Permit: TC-COM-1025-01811
Permit Details
Apply Date:
10/06/2025
Applicant:
Description:
ADDITION OF NEW EXTERIOR 3 STOP ELEVATOR, EGRESS STAIR AND CIRCULATION STRUCTURE TO EXISTING 3 STORY BUILDING. REMOVAL OF TWO EXISTING UTILITY STRUCTURES FROM A FORMER GROUND FLOOR RESTAURANT. THREE NEW DOOR OPENINGS IN EXISTING NORTH BUILDING WALL. NO INTERIOR WORK IN THE EXISTING BUILDING.
Permit Reviews
Permit Number - TC-COM-1025-01811
Permit Status: Needs resubmittal
Permit Description: ADDITION OF NEW EXTERIOR 3 STOP ELEVATOR, EGRESS STAIR AND CIRCULATION STRUCTURE TO EXISTING 3 STORY BUILDING. REMOVAL OF TWO EXISTING UTILITY STRUCTURES FROM A
FORMER GROUND FLOOR RESTAURANT. THREE NEW DOOR OPENINGS IN EXISTING NORTH BUILDING WALL. NO INTERIOR WORK IN THE EXISTING BUILDING.
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/07/2025 | COMMERCIAL REVIEW - FULL v.1 | 10/31/2025 | REQUIRES RESUBMIT |
| 11/26/2025 | COMMERCIAL REVIEW - FULL v.2 | 12/23/2025 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-1025-01811
Permit Status: Needs resubmittal
Permit Description: ADDITION OF NEW EXTERIOR 3 STOP ELEVATOR, EGRESS STAIR AND CIRCULATION STRUCTURE TO EXISTING 3 STORY BUILDING. REMOVAL OF TWO EXISTING UTILITY STRUCTURES FROM A
FORMER GROUND FLOOR RESTAURANT. THREE NEW DOOR OPENINGS IN EXISTING NORTH BUILDING WALL. NO INTERIOR WORK IN THE EXISTING BUILDING.
Total Outstanding Activity Conditions - 10
| Date | Name |
|---|---|
| 10/28/2025 | Elevator Designs must be submitted and approved prior to installation. |
| 10/28/2025 | ELEVATOR INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED. |
| 10/28/2025 | SPECIAL INSPECTION OF MASONRY CONSTRUCTION IS REQUIRED. |
| 10/28/2025 | NESHAP Permit is required. (Utilized with commercial demolition permits) |
| 10/28/2025 | SPECIAL INSPECTION OF POST-INSTALLED ANCHORS IS REQUIRED. |
| 10/28/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
| 10/28/2025 | Stair Designs must be submitted and approved prior to installation |
| 10/28/2025 | SPECIAL INSPECTION OF STEEL CONSTRUCTION IS REQUIRED. |
| 10/28/2025 | SPECIAL INSPECTION OF STEEL IS REQUIRED. |
| 12/18/2025 | Prior to issuance, confirm approval of Special Districts application SD-1125-00166. |
Conditions
Permit Number - TC-COM-1025-01811
Permit Status: Needs resubmittal
Permit Description: ADDITION OF NEW EXTERIOR 3 STOP ELEVATOR, EGRESS STAIR AND CIRCULATION STRUCTURE TO EXISTING 3 STORY BUILDING. REMOVAL OF TWO EXISTING UTILITY STRUCTURES FROM A
FORMER GROUND FLOOR RESTAURANT. THREE NEW DOOR OPENINGS IN EXISTING NORTH BUILDING WALL. NO INTERIOR WORK IN THE EXISTING BUILDING.
| Date | Description | Comments |
|---|---|---|
| 10/07/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |