Permit: TC-COM-0824-01700
Permit Details
Apply Date:
08/30/2024
Applicant:
Ted Herman
Description:
SUNNY DAYS - Tenant improvement to an existing masonry commercial building. The building is to remain as it is with no additional square footage added. The use will be retail.
Permit Reviews
Permit Number - TC-COM-0824-01700
Permit Status: Inspections
Permit Description: SUNNY DAYS - Tenant improvement to an existing masonry commercial building. The building is to remain as it is with no additional square footage added. The use will be retail.
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/09/2024 | COMMERCIAL REVIEW - LIMITED v.1 | 09/20/2024 | APPROVED |
Conditions
Permit Number - TC-COM-0824-01700
Permit Status: Inspections
Permit Description: SUNNY DAYS - Tenant improvement to an existing masonry commercial building. The building is to remain as it is with no additional square footage added. The use will be retail.
Date | Description | Comments |
---|---|---|
09/09/2024 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
10/09/2024 | Sewer/Wastewater |
Outstanding Inspections
Permit Status: Inspections
Permit Number: TC-COM-0824-01700
Permite Description: SUNNY DAYS - Tenant improvement to an existing masonry commercial building. The building is to remain as it is with no additional square footage added. The use will be retail.
Total Outstanding Inspections - 2
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2024 | COT - HCEL - Electrical Intermediate | N/A | Partial Pass | 12-20-24, no more than 3 mc cables tied together, fire foam any penetrations, properly secure mc cable to rafters/joists. Receptacle layout along walls is per plans and construction along these areas is okay to continue. Reschedule inspection for the listed above items mentioned. |
11/04/2024 | COT - LCPL - Plumbing Intermediate | N/A | Partial Pass | Underground plumbing in interior of suite. Ok to cover progress areas. |
Scheduled Inspections
Scheduled Inspections - TC-COM-0824-01700
Status: Inspections
Description: SUNNY DAYS - Tenant improvement to an existing masonry commercial building. The building is to remain as it is with no additional square footage added. The use will be retail.
Scheduled Date | Description | Entered By | Entered Date |
---|---|---|---|
12/23/2024 | COT - HCEL - Electrical Intermediate | Scheduled |