Permit Details

Status:
Needs Resubmittal
Type:
Commercial Building
Address:
702 S 6TH AV
Apply Date:
08/19/2024
Applicant:
Charles Pifer
Description:
INSTALLATION OF NEW LIMITED USE, LIMITED APPLICATION ELEVATOR / LIFT WITHIN EXISTING BUILDING INSTALLATION REQUIRES REWORK OF THE FOLLOWING: -EXTERIOR WALL OF BUILDING -MECHANICAL DUCTWORK -FIRE SPRINKLER SYSTEM -EXISTING FLOOR TRUSS JOISTS -CEILINGS -LIGHTING -NO CHANGE TO EGRESS OR EXITING

Permit Reviews

Permit Number - TC-COM-0824-01616
Permit Status: Needs resubmittal
Permit Description: INSTALLATION OF NEW LIMITED USE, LIMITED APPLICATION ELEVATOR / LIFT WITHIN EXISTING BUILDING INSTALLATION REQUIRES REWORK OF THE FOLLOWING: -EXTERIOR WALL OF BUILDING -MECHANICAL DUCTWORK -FIRE SPRINKLER SYSTEM -EXISTING FLOOR TRUSS JOISTS -CEILINGS -LIGHTING -NO CHANGE TO EGRESS OR EXITING
Start Date Submittal Complete Date Status  
08/19/2024 COMMERCIAL REVIEW - FULL v.1 09/20/2024 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0824-01616
Permit Status: Needs resubmittal
Permit Description: INSTALLATION OF NEW LIMITED USE, LIMITED APPLICATION ELEVATOR / LIFT WITHIN EXISTING BUILDING INSTALLATION REQUIRES REWORK OF THE FOLLOWING: -EXTERIOR WALL OF BUILDING -MECHANICAL DUCTWORK -FIRE SPRINKLER SYSTEM -EXISTING FLOOR TRUSS JOISTS -CEILINGS -LIGHTING -NO CHANGE TO EGRESS OR EXITING
Total Outstanding Activity Conditions - 7
Date Name
08/19/2024 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
09/12/2024 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
09/12/2024 Elevator Designs must be submitted and approved prior to ...
09/12/2024 ELEVATOR INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED.
09/12/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
09/12/2024 SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED.
09/12/2024 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.