Permit: TC-COM-0725-01410
Permit Details
Status:
Needs Resubmittal
Type:
Commercial Building
Address:
7101 E 22ND ST
Address NEW:
7101 E 22ND ST
Apply Date:
07/25/2025
Applicant:
Brett Gray
Description:
TI: Restaurant
Permit Reviews
Permit Number - TC-COM-0725-01410
Permit Status: Needs resubmittal
Permit Description: TI: Restaurant
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/25/2025 | COMMERCIAL REVIEW - FULL v.1 | 08/18/2025 | REQUIRES RESUBMIT |
| 10/17/2025 | COMMERCIAL REVIEW - FULL v.2 | 11/12/2025 | REQUIRES RESUBMIT |
| 11/25/2025 | COMMERCIAL REVIEW - FULL v.3 | 12/05/2025 | REQUIRES RESUBMIT |
Outstanding Activity Conditions
Permit Number - TC-COM-0725-01410
Permit Status: Needs resubmittal
Permit Description: TI: Restaurant
Total Outstanding Activity Conditions - 10
| Date | Name |
|---|---|
| 07/25/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. |
| 08/15/2025 | SPECIAL INSPECTION OF CONCRETE CONSTRUCTION IS REQUIRED. (SECTION 1705.3 AND TABLE 1705.3 CONCRETE MATERIAL SAMPLING AND TESTING, REBAR OBSERVATIONS. TAKE SET OF (3) CYLINDERS FOR EVERY 50 C.Y., BUT NOT LESS THAN ONE SET OF SAMPLES PER DAY'S WORK AND PER MIX.) |
| 08/15/2025 | SPECIAL INSPECTION OF POST-INSTALLED ANCHORS IS REQUIRED.(TABLE 1705.3) |
| 08/15/2025 | SPECIAL INSPECTION OF SEISMIC ANCHORAGE AND BRACING FOR NONSTRUCTURAL COMPONENTS IS REQUIRED. (SECTION 1705.13 AND 1705.14) |
| 08/15/2025 | SPECIAL INSPECTION OF SOILS IS REQUIRED.(FOUNDATION BEARING, EXCAVATION, FILL PLACEMENT.) |
| 08/15/2025 | A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. |
| 08/15/2025 | SPECIAL INSPECTION OF STEEL CONSTRUCTION IS REQUIRED. (SECTION 1705.2, AND AISC 360. PERIODIC OBSERVATIONS OF CONNECTION, ALL BRACED-FRAME CONNECTIONS, WELDERS & FIELD WELDING.) |
| 11/06/2025 | AIR BALANCING REPORT IS REQUIRED. |
| 11/06/2025 | Separate submittal to PC Industrial Wastewater Control is required for new interceptors and separators. Contact Kelsey.McMonagle@pima.gov or Adam.DeLaTorre@pima.gov for review and assessment of the proposed grease interceptor. |
| 11/06/2025 | WATER STERILIZATION REPORT IS REQUIRED. |
Conditions
Permit Number - TC-COM-0725-01410
Permit Status: Needs resubmittal
Permit Description: TI: Restaurant
| Date | Description | Comments |
|---|---|---|
| 07/25/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |