Permit: TC-COM-0725-01291
Permit Details
Status:
Issued
Type:
Commercial Building
Address:
800 E UNIVERSITY BL UNIT 106
Address NEW:
800 E UNIVERSITY BL UNIT 106
Apply Date:
07/02/2025
Applicant:
Joshua Stewart
Description:
New ADA Restroom, Plumbing, Mechanical, Electrical
Permit Reviews
Permit Number - TC-COM-0725-01291
Permit Status: Issued
Permit Description: New ADA Restroom, Plumbing, Mechanical, Electrical
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/15/2025 | ADMINISTRATIVE v.2 | 10/15/2025 | APPROVED |
| 04/30/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 05/05/2026 | APPROVED |
| 07/07/2025 | COMMERCIAL REVIEW - LIMITED v.1 | 07/21/2025 | APPROVED |
| 05/15/2026 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 05/20/2026 | APPROVED |
| 10/13/2025 | ADMINISTRATIVE v.1 | 10/13/2025 | REQUIRES RESUBMIT |
| 07/22/2025 | RESTAMP - COMMERCIAL v.1 | 07/23/2025 | APPROVED |
Conditions
Permit Number - TC-COM-0725-01291
Permit Status: Issued
Permit Description: New ADA Restroom, Plumbing, Mechanical, Electrical
| Date | Description | Comments |
|---|---|---|
| 07/07/2025 | Plans need to reflect Unit 106 | |
| 07/21/2025 | AIR BALANCING REPORT IS REQUIRED. | |
| 07/07/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 07/07/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-0725-01291
Permite Description: New ADA Restroom, Plumbing, Mechanical, Electrical
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2026 | COT - FCON - Alarm - Final | N/A | Not Applicable | |
| 04/27/2026 | COT - LCBU - Building Final | N/A | Re-inspection required | 4/27/26: Grab bars shall be no higher than 36" AFF per A117.1 (609.4.1), Mirror must be installed to verify height, floor sinks shall be sealed with approved method to prevent sewer gases from escaping, exterior hose-bib must be insulated and wrapped from UV protection, Refrigerant lines for condenser must be appropriately supported, seal sleeve on south exterior wall, 90 degree elbow required on condensate drain, UV coat all exterior plastic piping, Refrigerant locking caps required at condenser, exterior receptacle shall be WR, water heater installed is 3-phase (plans call for single phase with approved e;electrical connection) ( 3-phase will not work for this application with single phase connections). |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-0725-01291
Permit Description: New ADA Restroom, Plumbing, Mechanical, Electrical
Total Completed Inspections - 10
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2025 | COT - LCPL - Rough Soil | Passed | ||
| 12/29/2025 | COT - LCEL - Electrical Intermediate | Passed | ||
| 12/29/2025 | BULD - Electrical Clearance | Passed | Passed, OK to set new meter and begin service. | |
| 04/27/2026 | COT - FCON - Fire - Final | Passed | ||
| 04/27/2026 | COT - LCME - Mechanical Final | Passed | ||
| 04/27/2026 | COT - LCEL - Electrical Final | Passed | ||
| 04/27/2026 | COT - LCPL - Plumbing Final | Passed | ||
| 04/27/2026 | COT - FCON - Sprinkler - Final | Passed | ||
| 04/27/2026 | COT - LCEL - Grounding/Bonding | Passed | ||
| 04/29/2026 | COT - LCBU - Building Final | Passed | 4/29/2026 approved. All corrections were made. |