Permit: TC-COM-0723-01691
Permit Details
Apply Date:
07/12/2023
Applicant:
Adam Davidson
Description:
Repaired / Restore power to pedestal from recent trailer fire/. Provide a more detailed description of the scope of work./ See additional information We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal due to them looking warn and needing to be replaced. No signs of being affected by the fire present. 2. Was the pedestal replaced Like for Like? If not, provide details. The pedestal has not been replaced no replacement is necessary it only needed minor repairs. 3. What about the Grounding Electrode System? Current grounding system is up to code. 5. Is this a master metered system? Yes 6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref; 2018 IBC section 107.2.1, 2017 NEC The old mobile home has been completely removed and it is a empty lot. No mobile trailer is being installed at this time. / Please see the applicants plan review comment responses; . Provide a more detailed description of the scope of work. We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal due to them looking warn and needing to be replaced. No signs of being affected by the fire present. 2. Was the pedestal replaced Like for Like? If not, provide details. The pedestal has not been replaced no replacement is necessary it only needed minor repairs. 3. What about the Grounding Electrode System? Current grounding system is up to code. 5. Is this a master metered system? Yes 6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref; 2018 IBC section 107.2.1, 2017 NEC The old mobile home has been completely removed and it is a empty lot. No mobile trailer is being installed at this time.
Permit Reviews
Permit Number - TC-COM-0723-01691
Permit Status: Issued
Permit Description: Repaired / Restore power to pedestal from recent trailer fire/. Provide a more detailed description of the scope of work./ See additional information
We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal
due to them looking warn and needing to be replaced.
No signs of being affected by the fire present.
2. Was the pedestal replaced Like for Like? If not, provide details.
The pedestal has not been replaced no replacement is necessary it only needed minor
repairs.
3. What about the Grounding Electrode System?
Current grounding system is up to code.
5. Is this a master metered system?
Yes
6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref;
2018 IBC section 107.2.1, 2017 NEC
The old mobile home has been completely removed and it is a empty lot. No mobile trailer is
being installed at this time. / Please see the applicants plan review comment responses; . Provide a more detailed description of the scope of work.
We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal
due to them looking warn and needing to be replaced.
No signs of being affected by the fire present.
2. Was the pedestal replaced Like for Like? If not, provide details.
The pedestal has not been replaced no replacement is necessary it only needed minor
repairs.
3. What about the Grounding Electrode System?
Current grounding system is up to code.
5. Is this a master metered system?
Yes
6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref;
2018 IBC section 107.2.1, 2017 NEC
The old mobile home has been completely removed and it is a empty lot. No mobile trailer is
being installed at this time.
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/28/2023 | COMMERCIAL PDSD SIMPLE REVIEW v.2 | 08/03/2023 | APPROVED |
07/14/2023 | COMMERCIAL PDSD SIMPLE REVIEW v.1 | 07/19/2023 | REQUIRES RESUBMIT |
Outstanding Inspections
Permit Status: Issued
Permit Number: TC-COM-0723-01691
Permite Description: Repaired / Restore power to pedestal from recent trailer fire/. Provide a more detailed description of the scope of work./ See additional information
We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal
due to them looking warn and needing to be replaced.
No signs of being affected by the fire present.
2. Was the pedestal replaced Like for Like? If not, provide details.
The pedestal has not been replaced no replacement is necessary it only needed minor
repairs.
3. What about the Grounding Electrode System?
Current grounding system is up to code.
5. Is this a master metered system?
Yes
6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref;
2018 IBC section 107.2.1, 2017 NEC
The old mobile home has been completely removed and it is a empty lot. No mobile trailer is
being installed at this time. / Please see the applicants plan review comment responses; . Provide a more detailed description of the scope of work.
We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal
due to them looking warn and needing to be replaced.
No signs of being affected by the fire present.
2. Was the pedestal replaced Like for Like? If not, provide details.
The pedestal has not been replaced no replacement is necessary it only needed minor
repairs.
3. What about the Grounding Electrode System?
Current grounding system is up to code.
5. Is this a master metered system?
Yes
6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref;
2018 IBC section 107.2.1, 2017 NEC
The old mobile home has been completely removed and it is a empty lot. No mobile trailer is
being installed at this time.
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2023 | BULD - Electrical Clearance | N/A | Not Applicable | Approved RV pedestal breaker and receptacle replacement for space #37, Park has a master meter, no clearance required |
Completed Inspections
Permit Status: Issued
Permit Number: TC-COM-0723-01691
Permit Description: Repaired / Restore power to pedestal from recent trailer fire/. Provide a more detailed description of the scope of work./ See additional information
We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal
due to them looking warn and needing to be replaced.
No signs of being affected by the fire present.
2. Was the pedestal replaced Like for Like? If not, provide details.
The pedestal has not been replaced no replacement is necessary it only needed minor
repairs.
3. What about the Grounding Electrode System?
Current grounding system is up to code.
5. Is this a master metered system?
Yes
6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref;
2018 IBC section 107.2.1, 2017 NEC
The old mobile home has been completely removed and it is a empty lot. No mobile trailer is
being installed at this time. / Please see the applicants plan review comment responses; . Provide a more detailed description of the scope of work.
We have replaced the 2 outlets and breakers that feed them in the existing trailer pedestal
due to them looking warn and needing to be replaced.
No signs of being affected by the fire present.
2. Was the pedestal replaced Like for Like? If not, provide details.
The pedestal has not been replaced no replacement is necessary it only needed minor
repairs.
3. What about the Grounding Electrode System?
Current grounding system is up to code.
5. Is this a master metered system?
Yes
6. What is the Pedestal going to power? Has the burned mobile home been replaced? Ref;
2018 IBC section 107.2.1, 2017 NEC
The old mobile home has been completely removed and it is a empty lot. No mobile trailer is
being installed at this time.
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2023 | COT - LCEL - Electrical Final | Passed | Approved RV pedestal breaker and receptacle replacement for space #37, Park has a master meter, no clearance required |