Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Revision Fees Due
Type:
Commercial Building
Address:
1070 E AJO WY
Address NEW:
1070 E AJO WY
Apply Date:
06/05/2025
Applicant:
Arthur Martin
Description:
New commercial building for Carl's Restaurant located at 1070 E Ajo Way

Permit Reviews

Permit Number - TC-COM-0625-01102
Permit Status: Revision fees due
Permit Description: New commercial building for Carl's Restaurant located at 1070 E Ajo Way
Start Date Submittal Complete Date Status  
10/21/2025 COMMERCIAL REVIEW - FULL v.4 10/21/2025 REQUIRES RESUBMIT Review Details
10/22/2025 COMMERCIAL REVIEW - FULL v.5 10/22/2025 REQUIRES RESUBMIT Review Details
08/15/2025 COMMERCIAL REVIEW - FULL v.2 08/15/2025 APPROVED Review Details
07/15/2026 ADMINISTRATIVE v.1 07/15/2026 REQUIRES RESUBMIT Review Details
01/14/2026 ADMINISTRATIVE v.1 01/14/2026 REQUIRES RESUBMIT Review Details
08/06/2026 SPECIAL INSPECTION REVIEW v.1 08/10/2026 APPROVED Review Details
08/25/2026 BUILDING DEFERRED SUBMITTAL REVIEW v.1 08/26/2026 APPROVED Review Details
07/08/2026 SPECIAL INSPECTION REVIEW v.1 07/08/2026 REQUIRES RESUBMIT Review Details
01/02/2026 COMMERCIAL REVIEW - FULL v.7 01/13/2026 APPROVED Review Details
08/17/2026 SPECIAL INSPECTION REVIEW v.1 08/20/2026 APPROVED Review Details
11/13/2025 COMMERCIAL REVIEW - FULL v.6 12/04/2025 REQUIRES RESUBMIT Review Details
10/21/2026 COMMERCIAL REVIEW - FULL REVISION v.1 11/16/2026 APPROVED Review Details
07/09/2026 SPECIAL INSPECTION REVIEW v.2 07/15/2026 APPROVED Review Details
07/08/2026 ADMINISTRATIVE v.2 07/08/2026 APPROVED Review Details
09/04/2025 COMMERCIAL REVIEW - FULL v.3 09/26/2025 REQUIRES RESUBMIT Review Details
06/09/2025 COMMERCIAL REVIEW - FULL v.1 07/01/2025 REQUIRES RESUBMIT Review Details

Outstanding Activity Conditions

Permit Number - TC-COM-0625-01102
Permit Status: Revision fees due
Permit Description: New commercial building for Carl's Restaurant located at 1070 E Ajo Way
Total Outstanding Activity Conditions - 9
Date Name
01/12/2026 SPECIAL INSPECTION OF WATER-RESISTIVE BARRIER COATING IS REQUIRED.
06/23/2025 COUNTY HEALTH INSPECTION IS REQUIRED - PLEASE PROVIDE DOCUMENTATION THAT THE INSPECTION HAS BEEN COMPLETED AND PASSED.
07/13/2026 SPECIAL INSPECTION FOR EIFS
10/21/2025 SPECIAL INSPECTION FOR CONCRETE INSTALLATION IS REQUIRED.
10/21/2025 SPECIAL INSPECTION FOR SPECIAL GRADING, EXCAVATION AND FILLING IS REQUIRED.
10/21/2025 SPECIAL INSPECTION FOR WOOD FRAMED DIAPHRAGMS AND SHEAR WALLS IS REQUIRED.
11/17/2025 SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED.
12/04/2025 AIR BALANCING REPORT IS REQUIRED.
12/04/2025 WATER STERILIZATION REPORT IS REQUIRED.

Conditions

Permit Number - TC-COM-0625-01102
Permit Status: Revision fees due
Permit Description: New commercial building for Carl's Restaurant located at 1070 E Ajo Way
Date Description Comments
06/09/2025 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact.
06/09/2025 Plan review applications expire 180 days from date of submittal unless the permit has been issued. Permits expire 180 days after issuance or last approved inspection.
11/17/2025 An Outdoor Lighting Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
07/01/2025 Separate submittal to PC Industrial Wastewater Control is required for new or re-purposed interceptors and separators. Contact Kelsey.McMonagle@pima.gov or Adam.DeLaTorre@pima.gov for review and assessment of the proposed grease interceptor.
06/09/2025 Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900.
06/09/2025 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
08/19/2026 Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building.

Outstanding Inspections

Permit Status: Revision Fees Due
Permit Number: TC-COM-0625-01102
Permite Description: New commercial building for Carl's Restaurant located at 1070 E Ajo Way
Total Outstanding Inspections - 10
Last Inspection Date Description Inspector Results Comments
08/27/2026 BULD - Electrical Clearance N/A Partial Pass Partial pass. Clearance for TEP TMPC. 8/27/2026
09/09/2026 COT - LCEL - Grounding/Bonding N/A Partial Pass 9-9-26: partial pass for UFER only.
10/01/2026 COT - HCEL - Electrical Underground N/A Partial Pass
10/07/2026 COT - LCEL - Electrical Underground N/A Partial Pass 10/7/26: verified trench depth at 4' for 2-3" secondary electrical conduits/sweeps located on south side of building. Okay to backfill approximately 35' of trench using shading materials.
10/28/2026 COT - HCPL - Gas Pressure Test N/A Partial Pass Partial pass. Kitchen area approved. 10/28/2026
10/28/2026 COT - LCME - Mechanical Intermediate N/A Re-inspection required Will verify at above ceiling inspections. 10/28/2026
10/28/2026 COT - LCEL - Electrical Intermediate N/A Partial Pass Partial pass. In walls all areas approved. Okay to proceed with progress areas. 10/28/2026
08/27/2026 COT - LCPL - Plumbing Intermediate N/A Not Ready
11/05/2026 COT - HCBU - Interior Shear Bracing N/A Re-inspection required 11/5/26: add screws to the base of interior plywood FRP walls at 12"o.c. along sill plate and 8" o.c. at interior 1/2" drywall sill plates (12" o.c. In the field for both). Reschedule inspection when ready.
10/28/2026 COT - LCBU - Framing N/A Partial Pass Partial pass. In walls all areas approved for electrical and plumbing work. 10/28/2026

Completed Inspections

Permit Status: Revision Fees Due
Permit Number: TC-COM-0625-01102
Permit Description: New commercial building for Carl's Restaurant located at 1070 E Ajo Way
Total Completed Inspections - 8
Date Description Inspector Results Comments
09/09/2026 COT - LCBU - Preslab Passed 9/9/26: Pre-slab, Excavation & reinforcement on footers and slab on grade verified per foundation plan-S1 & Details. Also, Verified vapor barrier together with 6-5/8" and 2-7/8" hold down anchors per SW schedule. Okay for concrete placement.
09/09/2026 COT - LCBU - Excavation/Rebar/Zoning Passed 9/9/26: Excavation & reinforcement on footers and slab on grade verified per foundation plan-S1 & Details. Also, Verified vapor barrier together with 6-5/8" and 2-7/8" hold down anchors per SW schedule. Okay for concrete placement.
10/01/2026 COT - HCBU - Exterior Clips/Sheathing Passed
10/01/2026 COT - HCPL - Rough Soil Passed
10/01/2026 COT - LCPL - Yard Water Line Passed
10/01/2026 COT - LCBU - Roof Nailing Passed
10/06/2026 COT - HCPL - Sewer Passed 10/6/26: verified trench depth at 4' with a 4" sewer pipe under test. Okay to backfill approximately 120' of open trench using shading materials.
10/28/2026 COT - HCPL - Plumbing Roof Drains Passed Approved. All roof drains along with overflows through roof on test. 10/28/2026

Documents

File Name Document Type  
2026-10-14_NRD LETTER - OWNER CHANGES NARRATIVE TO BUILDING DEPT-2026-10-15_V1.PDF DOCUMENTS VIEW
2025-12-31_24157_CARL'S RESTAURANT, TUCSON, AZ - COMPLETE COMPILED SET - REV3_V1 (1).PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD (SSRS).PDF DOCUMENTS VIEW
2026-08-13_ 240848 - RED BUILT - EN - NRD REVIEWED_V1.PDF DOCUMENTS VIEW
2026-07-29_SPECIAL LIGHTING INSPECTION CERT SIGNED 7.28.2026-2026-08-03_V1.PDF DOCUMENTS VIEW
2026-01-23_STATEMENT AND SCHEDULE SPECIAL INSPECTIONS - NRD - BPA COMPLETE-2026-07-08_V1.PDF DOCUMENTS VIEW
2025-12-29_NRD LETTER - COMPILED RESPONSE TO COMMENTS - BUILDING_V1.PDF DOCUMENTS VIEW
2025-12-31_24157_CARL'S RESTAURANT, TUCSON, AZ - COMPLETE COMPILED SET - REV3_V1.PDF DOCUMENTS VIEW